6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1110 -
5.7.6 Setting
Setting of CLOCK (Function ID: 200301)
Setting item
Range
Unit
s
Contents
Default setting
value
Notes
Timezone
-14.00 - 14.00
hour
Time zone
0.00
TimeSyncSrc
--- / SNTP / BI /
IRIG-B
-
Time sync source
SNTP
Date_fmt
YYYYMMDD /
MMDDYYYY /
DDMMYYYY
-
YMD/MDY/DMY
YYYYMMDD
Date_delimiter
- / / / .
-
- or / or .
-
Time_delimiter
: / .
-
: or period
:
Sec_delimiter
. / ,
-
. or ,
.
SummerTime
Off / On
-
Summer time enable
Off
IS_UTC_base
Off / On
-
Is setting value base on UTC?
On
Start_Month
1 - 12
-
Start month
3
Start_Week
1 - 5
-
Start week
5
Start_Wday
--- / Sun. / Mon. / Tue.
/ Wed. / Thr. / Fri. /
Sat.
-
Start day of week
Sun.
Start_Hour
0 - 23
-
Start hour
1
End_Month
1 - 12
-
End month
10
End_Week
1 - 5
-
End week
5
End_Wday
--- / Sun. / Mon. / Tue.
/ Wed. / Thr. / Fri. /
Sat.
-
End day of week
Sun.
End_Hour
0 - 23
-
End hour
1
Setting of SNTP_SYNC (Function ID: 200A01)
Setting item
Range
Unit
s
Contents
Default setting
value
Notes
SNTP
Off / On
-
Enabling SNTP synchronization
On
Server1
0 - 255
-
IP address#1
0. 0. 0. 0
Server2
0 - 255
-
IP address#2
0. 0. 0. 0
Server3
0 - 255
-
IP address#3
0. 0. 0. 0
Server4
0 - 255
-
IP address#4
0. 0. 0. 0
Setting of BI_SYNC (Function ID: 202001)
Setting item
Range
Unit
s
Contents
Default setting
value
Notes
BI SYNC
Off / On
-
BI sync switch
Off
BI_ID
[Preferred ID]
-
Source BI Data ID
SYNC ADJ
-0.050 to 0.050
s
Time adjust factor
0.000
Setting of IRIG_SYNC (Function ID: 202101)
Setting item
Range
Unit
s
Contents
Default setting
value
Notes
IRIG SYNC
Off / On
-
IRIGB sync switch
Off
USE_BCDYEAR
Off / On
-
Use BCD year code
Off
USE_LOCALTIME
Off / On
-
Use local time
Off