Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1131 -
(iii) PLC program
Figure 7.4-5 shows the transmitter logic where the INT.DISCAR-S-A output command is given
to the DIN module; the output (DO) is connected to the input (DI) of the DOUT module in the
COMM_APPL function. The other output commands from the DISCAR and DEFCAR functions
should be connected in the COMM_APPL function. Figure 7.4-6 shows the receiver logic.
N=1 Frame
INT_DISCAR_S_A
INT.DISCAR-S-A
(436001 8000001B78)
DOUT_BOOL
FID
DTYPE
DID
ST
DI
COM_1_S
COM1-1_S
4A9001 800212EBB0
DIN_BOOL
FID
DTYPE
DID
DO
ST
Figure 7.4-5 Sample transmitter logic for COM_1 sub-communication channel
N=1 Frame
COM1_1_R1
DIN_BOOL
FID
DTYPE
DID
DO
ST
COM1-1_R1
(4A9001 8010051CF0)
DOUT_BOOL
FID
DTYPE
DID
ST
DI
INT_DISCAR_R1_A
INT.DISCAR-R1-A
436001 800000EBB5
Figure 7.4-6 Receiver logic for COM_1 sub-communication channel
Note: DIN_BOOL and DOUT_BOOL are used to import and export the information for
the data ID in bit type.