EasyManua.ls Logo

Toshiba GR200 Series - (ii) Single-phase-earth fault

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 93 -
(2.10-6)
As shown above, the positive-sequence impedance is used when determining settings for
phase faults.
Figure 2.10-1 Phase-to-phase fault
(ii) Single-phase-earth fault
Figure 2.10-2 shows the power system in the event of a single-phase-earth fault. It is very
difficult to measure precisely the distance to the fault point for a single-phase-earth fault. This
is because the impedance of the zero-sequence circuit including the earth return is generally
different from the positive-sequence impedance. Therefore, the faulted phase voltage is not
simply proportional to the faulted phase current.
Figure 2.10-2 Single-phase-earth fault
It is necessary to analyze the impedance seen by the relay in the event of a single-phase-
earth fault according to the method of symmetrical components. Figure 2.10-3 shows an
equivalent circuit for a single-phase-earth fault based on the method of symmetrical
components. If we define the positive-sequence, negative-sequence and zero-sequence voltages
as being V
1
F, V
2
F and V
0
F, then the voltage at the relaying point of each symmetrical circuit
will be given by the following equations based upon the assumption that the positive-sequence
Zs
VF
VF
Ib
Vc
Ic
Zm
Va
Vb
ZS
VaF
Ib
Vc
Ic
Va
Vb
ZG
Ia

Table of Contents

Related product manuals