logical signal using settings the [OP Mode ID265] etc. For example, the user wishes to record
the output level of the binary output circuit#1 (BO1) at the IO#1 slot, set its PLC monitoring
point 200B01 8002001112 for the setting [OP Mode ID265]; set the displaying name using the
[OP Mode Name265].
(iii) Additional triggers for the recording
Wishing to start the fault recorder except for the trip instruction, the user can use the PLC
connection points ADD_F.RECORD_TRIG1 to ADD_F.RECORD_TRIG4, respectively.
(iv) Time setting for Pre-fault
The instant before the trip is programmable using the setting [Pre-Fault Time] among 10s, 50s,
100s, 200s, 300s.
(v) Unit setting for the quantities
To change the units of power quantities, go to the metering function discussed in
Chapter
Metering function
.