- 1154 -
8.1.4 Scheme logic
The operation of the fault recorder can be directed by the TRC function, protection functions
(FC1 to FC40†), and the PLC function, as shown in Figure 8.1-3.
FC1_OPT_AR
FC1_OPT_BR
FC1_OPT_CR
FC1_OPT_ABR
FC1_OPT_BCR
FC1_OPT_CAR
From protection function #1(FC1)
FC1_OPT_AR
FC1_OPT_BR
FC1_OPT_CR
FC1_OPT_ABR
FC1_OPT_BCR
FC1_OPT_CAR
From protection function #2(FC2)
From protection function #40(FC40)
FC40_OPT_AR
FC40_OPT_BR
FC40_OPT_CR
FC40_OPT_ABR
FC40_OPT_BCR
FC40_OPT_CAR
Identifier signals
(FC*_OPT_*) coming
from protection functions
(FC*) are detected
changing the logic level
“0(Un-operated)” to
“1(Operated)”.
Quantities in the power system
Signals about the
operation modes in the
protection functions are
set.
Operation mode information recorded
when GEN.TRIP_ALARM signal is
generated in the TRC function
Figure 8.1-3 Fault record circuit
†Note: The correspondences table for the FC numbers are discussed in Chapter
Relay
application: Trip circuit
.