- 1166 -
Table 8.3-2 Recording number of logic signals depending on time settings
(ii) Number of logical signals
As mentioned earlier, the disturbance recorder can hold the traces of logic signals during the
recording time. Using settings [Binary Signal*], the user can select 256 logic signal arbitrary.
The logic signals that the user has selected should be termed with user’s preferred names using
settings [Binary Sig.Name*]. For example, ‘CB1-A_CLOSE’ signal of the PROT_COMM
function may be chosen to record using the setting [Binary Signal1]; we should term it ‘CB1-
A_CLOSE’ using the [Binary Sig.Name1]. Table 8.3-3 tabulates the default settings.