10.3.2 Trip circuit error (TC error)
(i) Error level
For the operation, the user can set the error level when the function detects the error
concerning the operation. Generally, the default error level is set at level 3 (Minor error), but
the user can program the level for the TCS16 using settings [CHK_TCS1:LVL] to
[CHK_TCS6:LVL]; then, set On for the setting [CHK_TCS1:Sw] to [CHK_TCS6:Sw].
(ii) Error message
When the function operates and detects error, an error message can be shown at the LED and
the LCD screen.
Table 10.3-3 Error messages provided by the supervisor in TCS
Item
Meaning of the information
TCx error
Detection of an error located at x
Error level
Minor error (Level 3)
Table 10.3-4 Detailed information in TCS
Display area
Meaning of the detailed information
N/A
(No message is displayed)