- 1310 -
10.5.7 Propagation delay error (Com Td)
Propagation delay on the communication can be monitored; it can be detected when the
propagation delay is examined beyond the setting. The delay error is issued when the delay is
detected for ten seconds.
(i) Error level
Generally, the default error level is set at level 3 (Minor error) when the delay is 6000 micro
seconds larger. However, the user can program the criterion time using settings
[CHK_TD_OVER1:Td] and [CHK_TD_OVER2:Td] in micro seconds; then, set On for the
settings [CHK_TD_OVER1:Sw] and [CHK_TD_OVER2:Sw] after set preferred error levels of
the settings [CHK_TD_OVER1:Lvl] and [CHK_TD_OVER2: Lvl]. The manufacturer sets ten
(10) seconds to detect the failure; it is reset with in a second when the failure is cleared.
(ii) Error message
When the function operates and detects error, an error message can be shown at the LED and
the LCD screen.
Table 10.5-15 Error messages provided by the supervisor in CHK_TD_OVER
Meaning of the information
Detection for delay time being over at X module
Table 10.5-16 Detailed information in Hexadecimal in CHK_TD_OVER
Meaning of the detailed information
Delay time expressed in the
hexadecimal
Setting time expressed in the hexadecimal
(No information is displayed)
(No information is displayed)
(No information is displayed)
(No information is displayed)