- 1380 -
11.3.8 Goose monitoring status in 61850 communication
IEDs are able to monitor the communication using GOOSE packets, which other IEDs have
sent their information via the network. If the IED can receive the GOOSE packets, the IED
can display them on the information list. Figure 11.3-33 illustrates an example of the GOOSE
monitoring list; it shows all IEDs have reported good status (OK) message, except one IED.
GOOSE Monitoring
11:12 1/320
GRZ200_Bay1 OK
GRT200_Bay1 OK
GRD200_Bay1 OK
GRL200_Bay1 NG
GRZ200_Bay2 OK
GRT200_Bay2 OK
GRD200_Bay2 OK
GRL200_Bay2 OK
GRZ200_Bay3 OK
GRT200_Bay3 OK
GRD200_Bay3 OK
GRL200_Bay3 OK
GRZ200_Bay99 OK
GRT200_Bay99 OK
GRD200_Bay99 OK
GRL200_Bay99 OK
SUB_ QUAL#0
SUB_ QUAL#1
SUB_ QUAL#2
SUB_ QUAL#3
SUB_ QUAL#4
SUB_ QUAL#5
SUB_ QUAL#6
SUB_ QUAL#7
SUB_ QUAL#8
SUB_ QUAL#9
SUB_ QUAL#10
SUB_ QUAL#11
SUB_ QUAL#316
SUB_ QUAL#317
SUB_ QUAL#318
SUB_ QUAL#319
Figure 11.3-33 Screen example of GOOSE Monitoring
Note: The IED shall be managed with own subscription information to receive the
GOOSE packets regarding the other IEDs. Thus, the user should edit the
subscription contents (see Figure 11.3-21). The LCD displays the statuses based
on that the user has edited the list of the subscription contents.
Note: Jump to
Monitoring sub-menu
(see Chapter
User interface
) to display the GOOSE
mentoring screen. The user can also find the GOOSE information on the test
screen on GR-TIEMS.
On the LCD screen, the user can find either OK or NG message regarding other IEDs. The
OK/NG message is generated with the information of the GOOSE packet received. Table 11.3-9
illustrates the messages displayed on LCD screen and GR-TIEMS screen.