6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1414 -
FUN
Function type (FUN) is set referring to the Table 11.4-4. The FUN can be set to 0 to 255.
When clicking the Change all FUNs on the Common setting screen, all FUNs are changed
to the setting values at Common setting.
COT
Cause of Transmission (COT) of the frame is set. Not only one COT but two or more COT
can be selected each No. (frame). COT setting pattern and COT supplemented the frame
are according to Table 11.4-6. Though, the COT=9 (General Interrogation) cannot be
selected.
SCL Measurement Name/Measurement Description
The Data ID corresponding to a measurand is required to select.
Coefficient
Set the conversion coefficient, multiplied the power system quantities by, using floating-
point number. The SCL is a value which the power system quantity specified as above is
multiplied by this setting value.