6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1491 -
(i) CB operation
Figure 12.11-2 shows how to open CB (Off position).
Control
10:48 1/6
_Circuit Breaker >
SPOS >
DPOS >
TPOS >
Software Switch >
Auto Sequence >
DPOS_SYN_Dev1
10:48
Control execution
Push O button
Select control POS:
On
CANCEL:Operation stop
DPOS_SYN_Dev1
10:48
Selecting...
DPOS_SYN_Dev1
10:48
Current status:
On
Select control POS:
_Off
Change start?
ENTER:Yes CANCEL:No
[
ENTER]
Double
responses?
DIR mode
SBO mode
Output the command
Executing screen
Waiting for the
second response
Selecting succeeded.
Selecting failed.
DPOS_SYN_Dev1
10:48
Operation failed.
CAUSE:
Select failed.
Control
10:48 1/6
_DPOS_SYN_Dev1 >
On
[
ENTER]
[
ENTER]
DPOS_SYN_Dev1
10:48
Controlling...
CANCEL: Operation stop
DPOS_SYN_Dev1
10:48
Operation canceled.
[CANCEL]
DPOS_SYN_Dev1
10:48
Operation failed.
CAUSE:
Select failed.
Cancel failed
Cancel succeeded.
DPOS_SYN_Dev1
10:48
Operation completed.
[CANCEL]
Time out
1
DPOS_SYN_Dev1
10:48
Operation failed.
CAUSE:
Time limit over.
[ ]
[ ]
[ ]
[ ]
Control
10:48 1/6
_Circuit Breaker >
SPOS >
DPOS >
TPOS >
Software Switch >
Auto Sequence >
Control
10:48 1/6
_Circuit Breaker >
SPOS >
DPOS >
TPOS >
Software Switch >
Auto Sequence >
Open
Controlling failed
[ ]
Control
10:48 1/6
_Circuit Breaker >
SPOS >
DPOS >
TPOS >
Software Switch >
Auto Sequence >
O
Figure 12.11-2 Operation for opening CB
1
Note: Time out will occur if no responses come from CB device.
2
Note: For control Circuit breaker, the user should connect DPSY01 function with
circuit breakers using binary IO modules. See chapter
Control and monitoring
application: Double position controller with synchronizing-checking (DPSY)
.