Toshiba GR200 Series - Step6: Write settings with altered code; To write the settings corresponding to the altered code, use the GR-TIEMS. For example, after rated current changed to 1 A, rewrite the setting items into the IED using the altered ordering code (see Figure 13.4-1 about the altered code; in this examp...

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1501 -
Information
10:48 1/9
[IED TYPE]
GRL200
__-1033-1J2-2E
[Serial No.]
No XXXXXXX123
Line protection IED
GRL200
-11-224-12-1J-30-120
5A
50 / 60
100-120
110-250
Month, Year
****** ** ***
Rated current (In) on the nameplate: 5A rated set in the Manufacture
TOSHIBA ENERGY SYSTEMS & SOLUTIONS CORPORATION
Code at
Positon K
Rated
current
1
1A
2
5A
Rated current (In) in the IED: 1A rated changed by the user
Original code
Altered code
-11-224-12-1J-30-110
Figure 13.4-1 How to check the changed rated current with the altered code
Note: For the LCD screen operation, see
Chapter User interface: Information sub-menu
.
Note: To know how to read the code, refer to the preceding section
Unpack and
inspection of hardware and software
.
Step6: Write settings with altered code
To write the settings corresponding to the altered code, use the GR-TIEMS. For
example, after rated current changed to 1A, rewrite the setting items into the IED
using the altered ordering code (see Figure 13.4-1 about the altered code; in this
example: GRL200-11-224-12-1J-30-110-1033-1J2-2E). Figure 13.4-2 shows how to
write the settings.