- 1509 -
Test operations
The user can change IED to for Test mode by the operations on the IED front panel with
Main/Sub menus, as shown in Figure 14.4-1.
Record
Monitoring
Setting
IO Setting
Control
Time
Main Menu Sub-menu Sub-menu Sub-menu Sub-menu
Test Mode
TestFlag-EN
Mode Change
Signal Monitoring
Test Option
Function Test
Binary Input (Slot#n)
Binary Output (Slot#n)
Simultaneous Fault
Information
Security Setting
Login/Logout
S-TestFlagCancel
GOSNDBLK
GOSBUBLK
A.M.F.
Local-Test
Loop-Test
Open 1
Open 2
CLP-Test
DIFL-STUB-Test
ZS-Test.CTRL
ZS-Offset.CTRL
ZS-Test.XAngle
ZG-Test.XAngle
THM-Test
THM-IP
SOTF-Test
STUB-Test
UV-Test
UVS-Test
SHOTNUM-Test
SYNC01-Test
SYNC02-Test
MDCTRL-EN
MDCTRL-SELRST
MDCTRL-EXERST
BI*F OP
SLOT*-BI01-SET
SLOT*-BI02-SET
SLOT*-BI03-SET
…..
BO*F OP
SLOT*-BO01-SET
SLOT*-BO02-SET
SLOT*-BO03-SET
…..
Figure 14.4-1 Structure of test menu
Note: The structure and the contents about sub-menus depend on the software.
14.4.1 Test for communication
(i) GOOSE sending block (GOSNDBLK)
This is used for selecting or disabling the GOOSE sending information where there is a conflict
in communication with another active IED while sending a GOOSE signal.