6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1586 -
(PIXIT Ed.1&Ed.2)
5. PIXIT FOR SERVER MODEL
ID
Ed
Description
Value / Clarification
Sr1
1,2
Which analogue value (MX) quality bits are
supported (can be set by server)
Validity:
Y Good,
Y Invalid,
N Reserved,
Y Questionable
Y* Overflow
Y* OutofRange
N BadReference
N Oscillatory
Y* Failure
N OldData
Y* Inconsistent
N Inaccurate (OnlyHz)
Source:
Y Process
* Supports only for GBU DCAI
Model
Sr2
1,2
Which status value (ST) quality bits are
supported
(can be set by server)
Validity:
Y Good,
Y Invalid,
N Reserved,
Y Questionable
N BadReference
Y Oscillatory
Y Failure
Y OldData
Y Inconsistent
N Inaccurate
Source:
N Substituted
Y Test
N OperatorBlocked
Sr3
-
What is the maximum number of data object
references in one GetDataValues request
Deprecated
Sr4
-
What is the maximum number of data object
references in one SetDataValues request
Deprecated
Sr5
1
Which Mode values are supported
On Y
Blocked N
Test Y
Test/Blocked N
Off N
<additional items>
The order of interpretation of write requests
involving a list of variables.
Front-to-back order. This might
influence on write request
involving RptEna and other
variables in the same RCB.