6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1594 -
(PIXIT Ed.1&Ed.2)
14. PIXIT FOR CONTROL MODEL
ID
Ed
Description
Value / Clarification
Ct1
-
What control models are supported
(compare ICD file enums for Ed2)
DOns: Y
SBOns: Y
DOes: Y
SBOes: Y
Ct2
1,2
Is the control model fixed, configurable and/or
dynamic
Fixed
Ct3
-
Is TimeActivatedOperate supported (compare
PICS or SCL)
Deprecated
Ct4
-
Is operate-many” supported (compare
sboClass)
Deprecated
Ct5
1
Will the DUT activate the control output when
the test attribute is set in the SelectWithValue
and/or Operate request (when N test procedure
Ctl2 is applicable)
Y
Ct6
-
What are the conditions for the time (T)
attribute in the SelectWithValue and/or
Operate request
Deprecated
Ct7
-
Is pulse configuration supported (compare
pulseConfig)
Deprecated
Ct8
1
What is the behaviour of the DUT when the
check conditions are set
Is this behavior fixed, configurable, online
changeable
Y synchrocheck
Y interlock-check
Both bits are checked.
(NOTE) The result of Opening
operation (ctval = F) is
not Influenced by
SynchroCheck bit.
This behavior is fixed.