- 1594 -
(PIXIT Ed.1&Ed.2)
14. PIXIT FOR CONTROL MODEL
What control models are supported
(compare ICD file enums for Ed2)
DOns: Y
SBOns: Y
DOes: Y
SBOes: Y
Is the control model fixed, configurable and/or
dynamic
Is TimeActivatedOperate supported (compare
PICS or SCL)
Is “operate-many” supported (compare
sboClass)
Will the DUT activate the control output when
the test attribute is set in the SelectWithValue
and/or Operate request (when N test procedure
Ctl2 is applicable)
What are the conditions for the time (T)
attribute in the SelectWithValue and/or
Operate request
Is pulse configuration supported (compare
pulseConfig)
What is the behaviour of the DUT when the
check conditions are set
Is this behavior fixed, configurable, online
changeable
Y synchrocheck
Y interlock-check
Both bits are checked.
(NOTE) The result of Opening
operation (ctval = F) is
not Influenced by
SynchroCheck bit.
This behavior is fixed.