6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1597 -
(PIXIT Ed.1&Ed.2)
14. PIXIT FOR CONTROL MODEL(Continued)
ID
Ed
Description
Value / Clarification
Ct17
1
Does the IED accept a Select/SelectWithValue
from the same client when the control object is
already selected (Tissue #334)
SBOns: N
SBOes: N
Ct18
1,2
Is for SBOes the internal validation performed
during the SelectWithValue and/or Operate
step
Yes for both SelectWithValue and
Operate
Ct19
-
Can a control operation be blocked by Mod=Off
or [On-]Blocked (Compare PIXIT-Sr5)
Deprecated
Ct20
1,2
Does the IED support local / remote operation
Y
Ct21
1,2
Does the IED send an InformationReport with
LastApplError as part of the Operate response-
for control with normal security
SBOns: N
DOns: N
Ct22
2
How to force a parameter-change-in-
execution
N.A.
Ct23
1,2
How many SBOns/SBOes control objects can be
selected at the same time?
SBOns: n = 1
SBOes: n = 1
Ct24
1,2
Can a controllable object be forced to keep its
old state e.g. Internal Controllable Objects may
not be accessible to force this, whereas a switch
like Circuit Breaker outside the DUT can?
Y
Need PLC Logic customization.
Ct25
1,2
When CDC=DPC is supported, is it possible to
have DPC (Controllable Double Point) go to the
intermediate state? (00)
Y
Ct26
1,2
Name a DOes point (if any) with a finite
operate timeout and specify the timeout
(in milliseconds)
The timeout time is setting.
One example,
DPSY01-RST
Default value is 300[ms]
(10[ms]-1000[ms])
Ct27
2
Does the IED support control objects with
external signals?
DOns: N
SBOns: N
DOes: N
SBOes: N