(PIXIT Ed.1&Ed.2)
14. PIXIT FOR CONTROL MODEL(Continued)
Does the IED accept a Select/SelectWithValue
from the same client when the control object is
already selected (Tissue #334)
Is for SBOes the internal validation performed
during the SelectWithValue and/or Operate
step
Yes for both SelectWithValue and
Operate
Can a control operation be blocked by Mod=Off
or [On-]Blocked (Compare PIXIT-Sr5)
Does the IED support local / remote operation
Does the IED send an InformationReport with
LastApplError as part of the Operate response-
for control with normal security
How to force a “parameter-change-in-
execution”
How many SBOns/SBOes control objects can be
selected at the same time?
SBOns: n = 1
SBOes: n = 1
Can a controllable object be forced to keep its
old state e.g. Internal Controllable Objects may
not be accessible to force this, whereas a switch
like Circuit Breaker outside the DUT can?
Y
Need PLC Logic customization.
When CDC=DPC is supported, is it possible to
have DPC (Controllable Double Point) go to the
intermediate state? (00)
Name a DOes point (if any) with a finite
operate timeout and specify the timeout
(in milliseconds)
The timeout time is setting.
One example,
DPSY01-RST
Default value is 300[ms]
(10[ms]-1000[ms])
Does the IED support control objects with
external signals?
DOns: N
SBOns: N
DOes: N
SBOes: N