- 1681 -
Functional Data (5/7)
Non-directional and Directional Negative Sequence Phase Overcurrent (NOC) Protection
1
st
, 2
nd
, 3
rd
, 4
th
Definite time NOC threshold
0.02 to 50.00A in 0.01A steps (1A rating)
0.10 to 250.00A in 0.01A steps (5A rating)
1
st
, 2
nd
, 3
rd
, 4
th
Inverse time NOC threshold
0.02 to 5.00A in 0.01A steps (1A rating)
0.10 to 25.00A in 0.01A steps (5A rating)
Non Directional / Forward / Backward
0 to 180° in 1° steps (3I0 lags for −3V0)
0.5 to 25.0V in 0.1V steps
DT / IEC-NI / IEC-VI / IEC-EI / UK-LTI / IEEE-MI / IEEE-
VI / IEEE-EI / US-CO2 / US-CO8 / Original
0.00 to 300.00s in 0.01s steps
IDMTL Time Multiplier Setting TMS
0.010 to 50.000 in 0.001 steps
Definite Time or Dependent Time
0.00 to 300.00s in 0.01s steps
Reset Time Multiplier Setting RTMS
0.010 to 50.000 in 0.001 steps
Second harmonic detection
Inrush current thresholds
0.10 to 5.00A in 0.01A steps (1A rating)
0.5 to 25.0A in 0.1A steps (5A rating)
Thermal overload Protection
Thermal setting (THM = k.IFLC)
0.40 – 2.00A in 0.01A steps (1A rating)
2.0 – 10.0A in 0.1A steps (5A rating)
0.5 – 500.0mins in 0.1min steps
OFF, 50% to 100% in 1% steps
0.00 – 1.00A in 0.01A steps (1A rating)
0.0 – 5.0A in 0.1A steps (5A rating)
Broken Conductor Detection
Broken conductor threshold
0.10 to 1.00 in 0.01 steps
0.00 to 300.00s in 0.01s steps
Phase Overvoltage Protection
1
st
, 2
nd
overvoltage threshold
1.0 to 220.0V in 0.1V steps
0.00 to 300.00s in 0.01s steps
IDMTL Time Multiplier Setting TMS
0.010 to 100.000 in 0.001 steps
0.0 to 300.0s in 0.1s steps
Phase to Phase Overvoltage Protection
1
st
, 2
nd
overvoltage threshold
1.0 to 220.0V in 0.1V steps
0.00 to 300.00s in 0.01s steps
IDMTL Time Multiplier Setting TMS
0.010 to 100.000 in 0.001 steps
0.0 to 300.0s in 0.1s steps