6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1682 -
Functional Data (6/7)
Phase Undervoltage Protection
1
st
, 2
nd
undervoltage threshold
5.0 to 130.0V in 0.1V steps
Delay type
DTL, IDMT, Original
Drop-out/pick-up ratio
100 to 120% in 1% steps
DTL delay
0.00 to 300.00s in 0.01s steps
IDMTL Time Multiplier Setting TMS
0.010 to 100.000 in 0.001 steps
Reset delay
0.0 to 300.0s in 0.1s steps
Undervoltage block threshold
5.0 to 20.0V in 0.1V steps
Undervoltage block delay
0.00 to 300.00s in 0.01s steps
Phase to Phase Undervoltage Protection
1
st
, 2
nd
undervoltage threshold
5.0 to 130.0V in 0.1V steps
Delay type
DTL, IDMT, Original
Drop-out/pick-up ratio
100 to 120% in 1% steps
DTL delay
0.00 to 300.00s in 0.01s steps
IDMTL Time Multiplier Setting TMS
0.010 to 100.000 in 0.001 steps
Reset delay
0.0 to 300.0s in 0.1s steps
Undervoltage block threshold
5.0 to 20.0V in 0.1V steps
Undervoltage block delay
0.00 to 300.00s in 0.01s steps
Under/Over Frequency Protection
1st - 4th under/overfrequency threshold
(Fnom 10.00Hz) (Fnom + 10.00Hz) in 0.01Hz steps
Fnom: nominal frequency
DTL delay:
0.00 300.00s in 0.01s steps
Frequency UV Block
40.0 100.0V in 0.1V steps

Table of Contents