6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1683 -
Functional Data (7/7)
Autoreclosing
Number of shots
1 to 5 shots
Dead time for single-phase autoreclose
0.01 to 300.00s in 0.01s steps
Dead time for three-phase autoreclose
0.01 to 300.00s in 0.01s steps
Multi-shot dead line time
0.01 to 300.00s in 0.01s steps
Reclaim time
0.0 to 600.0s in 0.1s steps
Pulse width of reclosing signal output
0.01 to 10.00s in 0.01s steps
Autoreclose reset time
0.01 to 310.00s in 0.01s steps
Reset time for developing fault
0.01 to 300.00s in 0.01s steps
Follower breaker autoreclose delay time
0.01 to 300.00s in 0.01s steps
Voltage and Synchronism Check
Synchronism check angle
0° to 75° in 1° steps
UV element
10 to 150V in 1V steps
OV element
10 to 150V in 1V steps
Busbar or line dead check
10 to 150V in 1V steps
Busbar or line live check
10 to 150V in 1V steps
Synchronism check time
0.01 to 100.00s in 0.01s steps
Voltage check time
0.01 to 100.00s in 0.01s steps
Voltage Transformer Failure Supervision
Undervoltage element (phase-to-phase)
50 to 100V in 1V steps
Undervoltage element (phase-to-earth)
10 to 60V in 1V steps
Current change detection element
0.1A fixed (1A rating)
0.5A fixed (5A rating)
Residual voltage element
20V fixed
Residual current element
Common use with earth fault detection element
Fault Locator
Line reactance and resistance setting
0.0 to 999.9 in 0.1 steps (1A rating)
0.00 to 199.99 in 0.01 steps (5A rating)
Line length
0.0 to 399.9km in 0.1km steps
Correction factor of impedance between lines
80 to 120% in 1% steps
Correction factor of impedance between in
each phase
80 to 120% in 1% steps
Accuracy
±0.4km (up to 20km, without fault at near end)
±2% (up to 399.9km, without fault at near end)
Minimum measuring cycles
2.5 cycles
Metering Function
AC current
Accuracy 0.5% (at rating)
AC voltage
Accuracy 0.5% (at rating)
Energy (Wh, varh)
Accuracy 1.0% (at rating)
Power (P, Q)
Accuracy 1.0% (at rating when power quantities being fed)
Frequency
Accuracy 0.03%
Time Synchronisation
Protocol
SNTP