- 1683 -
Functional Data (7/7)
Dead time for single-phase autoreclose
0.01 to 300.00s in 0.01s steps
Dead time for three-phase autoreclose
0.01 to 300.00s in 0.01s steps
Multi-shot dead line time
0.01 to 300.00s in 0.01s steps
0.0 to 600.0s in 0.1s steps
Pulse width of reclosing signal output
0.01 to 10.00s in 0.01s steps
0.01 to 310.00s in 0.01s steps
Reset time for developing fault
0.01 to 300.00s in 0.01s steps
Follower breaker autoreclose delay time
0.01 to 300.00s in 0.01s steps
Voltage and Synchronism Check
Busbar or line dead check
Busbar or line live check
0.01 to 100.00s in 0.01s steps
0.01 to 100.00s in 0.01s steps
Voltage Transformer Failure Supervision
Undervoltage element (phase-to-phase)
Undervoltage element (phase-to-earth)
Current change detection element
0.1A fixed (1A rating)
0.5A fixed (5A rating)
Common use with earth fault detection element
Line reactance and resistance setting
0.0 to 999.9 in 0.1 steps (1A rating)
0.00 to 199.99 in 0.01 steps (5A rating)
0.0 to 399.9km in 0.1km steps
Correction factor of impedance between lines
Correction factor of impedance between in
each phase
±0.4km (up to 20km, without fault at near end)
±2% (up to 399.9km, without fault at near end)
Accuracy 0.5% (at rating)
Accuracy 0.5% (at rating)
Accuracy 1.0% (at rating)
Accuracy 1.0% (at rating when power quantities being fed)