- 1711 -
2-1. Type using ring terminals and 110-250 Vdc
Type using compression terminals
Type using ring terminals
Figure-11.C illustrates external connection around the power supply module (PWS). During dielectric
voltage testing, a short-wire and a short-bar attached on the PSW shall be carefully handled; follow
the below instructions (1) and (2).
(1) The short-wire between terminal screw No.35 and No.36
✓ Remove the short-wire for undertaking the dielectric voltage test. If the short-wire is not
removed, the IED will be damaged.
✓ After the test, reconnect the short-wire to the original positons.
(2) The Short-bar between terminal screw No.37 and FG
✓ Never remove the short-bar. If the short-bar is removed, the IED will be damaged.
Figure-11.C A short-wire and a short-bar, around the PWS, for Type using ring terminals and 110-250Vdc