EasyManua.ls Logo

Toshiba GR200 Series - 2.10.11 Setting

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 155 -
2.10.11 Setting
Distance common(Function ID: 432001)
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
IcC
Z-IcC
0.00 -
1.00
0.00 -
5.00
A
Charging current compensation for ZG and ZS
0.00
0.00
Z-Vn
100 - 120
V
Rated voltage for ZG and ZS
110
Z-IcC.EN
Off / On
-
Charging current compensation use or not for
ZG and ZS
Off
Z1CNT-TPBlk
Off / On
-
Z1 trip block when main-protection is out-of-
service
Off
Z1CNT-INSTOP
Off / On
-
Z1 instant trip when main-protection is out-of-
service
Off
Z1CNT-3PTP
Off / On
-
Z1 3-phases trip when main-protection is out-
of-service
Off
Z1CNT-ARCBlk
Off / On
-
arc block by Z1 operation when main-
protection is out-of-service
Off

Table of Contents