6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
157
ZS (Function ID 430001
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
Output
Z1S-MSDET
Off / On
-
Multi-phase or non-earth-fault condition is
used or not
On
Z1S-PSBBlk
Non / Block
-
Z1S operation blocked or not by PSB detection
Block
Z1S-LEBlk
Non / Block
-
Z1S blocked or not by Load encroachment
Non
Z1S-ARCBlk
Non / Block
-
Autoreclose execution block by Z1S-trip
Non
Z1S-OCFS-EN
Off / On
-
Fail-safe OC for Z1S-trip
Off
OCF1S
0.02 -
5.00
0.10 -
25.00
A
Fail-safe OC operation level for Z1S-trip
0.20
1.00
Z1S-SOTF
Off / On
-
SOTF using Z1S
Off
Z2S
Z2S-Dir
Forward / Reverse /
NonDir
-
Z2S directional characteristic
Forward
Mho
Z2S-Mho.Angle
30 - 90
deg
Z2S mho characteristic angle (for Mho)
85
Z2S-Mho.Reach
0.10 -
500.00
0.01 -
100.00
-
Z2S mho reach (for Mho)
20.00
4.00
Z2S-MhoX.EN
Off / On
-
Z2S reactance reach use or not (for Mho)
Off
Z2S-X.Reach
0.10 -
500.00
0.01 -
100.00
-
Z2S reactance reach
20.00
4.00
Z2S-MhoR.EN
Off / On
-
Z2S resistive reach use or not (for Mho)
Off
Z2S-R.Angle
30 - 90
deg
Z2S resistive reach characteristic angle
75
Z2S-R.Reach
0.10 -
500.00
0.01 -
100.00
-
Z2S resistive reach
25.50
5.10
Z2S-
MhoDX.EN
Off / On
-
Z2S directional-X characteristic use or not (for
Mho)
Off
Z2S-DX.Angle
0 - 60
deg
Z2S directional-X characteristic angle
30
Quad
Z2S-X.Reach
0.10 -
500.00
0.01 -
100.00
-
Z2S reactance reach
20.00
4.00
Z2S-R.Angle
30 - 90
deg
Z2S resistive reach characteristic angle
75
Z2S-R.Reach
0.10 -
500.00
0.01 -
100.00
-
Z2S resistive reach
25.50
5.10
Z2S-DX.Angle
0 - 60
deg
Z2S directional-X characteristic angle
30
Z2S-DR.Angle
0 - 60
deg
Z2S directional-R characteristic angle (for
Quad)
5
TZ2S
0.00 - 100.00
s
Z2S operation delay time
0.30
Output
Z2S-MSDET
Off / On
-
Multi-phase or non-earth-fault condition is
used or not
Off
Z2S-PSBBlk
Non / Block
-
Z2S operation block or not by PSB detection
Non
Z2S-LEBlk
Non / Block
-
Z2S blocked or not by Load encroachment
Non
Z2S-ARCBlk
Non / Block
-
Autoreclose execution block by Z2S-trip
Block
Z2S-OCFS-EN
Off / On
-
Fail-safe OC for Z2S-trip
Off
OCF2S
0.02 -
5.00
0.10 -
25.00
A
Fail-safe OC operation level for Z2S-trip
0.20
1.00
Z2S-SOTF
Off / On
-
SOTF using Z2S
Off
Z3S
Z3S-Dir
Forward / Reverse /
NonDir
-
Z3S directional characteristic
Forward
Mho
Z3S-Mho.Angle
30 - 90
deg
Z3S mho characteristic angle (for Mho)
85
Z3S-Mho.Reach
0.10 -
500.00
0.01 -
100.00
-
Z3S mho reach (for Mho)
30.00
6.00
Z3S-MhoX.EN
Off / On
-
Z3S reactance reach use or not (for Mho)
Off
Z3S-X.Reach
0.10 -
500.00
0.01 -
100.00
-
Z3S reactance reach
30.00
6.00
Z3S-MhoR.EN
Off / On
-
Z3S resistive reach use or not (for Mho)
Off
Z3S-R.Angle
30 - 90
deg
Z3S resistive reach characteristic angle
75
Z3S-R.Reach
0.10 -
500.00
0.01 -
100.00
-
Z3S resistive reach
25.50
5.10