6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 164 -
ZG (Function ID 431001
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
Z1G-Krm
0 - 1000
%
Zero phase current factor, Adjacent line
R0m/R1
0
Z1G-Kxm
0 - 1000
%
Zero phase current factor, Adjacent line
X0m/X1
0
TZ1G
0.00 - 100.00
s
Z1G operation delay time
0.00
Z1G-CovCoeff
1.5 - 10.0
-
Covered characteristic size coefficient
1.5
Output
Z1G-EFL
Off / On
-
EFL operation condition used or not for Z1G
operation
On
Z1G-MPFBlk
Non / Block
-
Z1G operation block or not in multi phase fault
Block
Z1G-PSBBlk
Non / Block
-
Z1G operation block or not by PSB detection
Block
Z1G-LEBlk
Non / Block
-
Load encroachment enable
Non
Z1G-LPBlk
Non / Block
-
Z1G leading phase operation block
Non
Z1G-TPMD
1P / 3P
-
Z1G trip mode, phase segregated trip or 3-
phase trip
1P
Z1G-ARCBlk
Non / Block
-
Autoreclose execution block by Z1G-trip
Non
Z1G-OCFS-EN
Off / On
-
Fail-safe OC for Z1G-trip
Off
OCF1G
0.02 - 5.00
0.10 -
25.00
A
Fail-safe OC operation level for Z1G-trip
0.20
1.00
Z1G-SOTF
Off / On
-
SOTF using Z1G
Off
Z2G
Z2G-Dir
Forward / Reverse /
NonDir
-
Z2G direction to protect
Forward
Mho
Z2G-Mho.Angle
30 - 90
deg
Z2G mho characteristic angle (for Mho)
85
Z2G-
Mho.Reach
0.10 -
500.00
0.01 -
100.00
-
Z2G mho reach (for Mho)
20.00
4.00
Z2G-MhoX.EN
Off / On
-
Z2G reactance reach use or not (for Mho)
Off
Z2G-X.Reach
0.10 -
500.00
0.01 -
100.00
-
Z2G reactance reach
20.00
4.00
Z2G-MhoR.EN
Off / On
-
Z2G resistive reach use or not (for Mho)
Off
Z2G-R.Angle
30 - 90
deg
Z2G resistive reach characteristic angle
75
Z2G-R.Reach
0.10 -
500.00
0.01 -
100.00
-
Z2G resistive reach
25.50
5.10
Z2G-
MhoDX.EN
Off / On
-
Z2G directional-X characteristic use or not (for
Mho)
Off
Z2G-DX.Angle
0 - 60
deg
Z2G directional-X characteristic angle
30
Quad
Z2G-X.Reach
0.10 -
500.00
0.01 -
100.00
-
Z2G reactance reach
20.00
4.00
Z2G-R.Angle
30 - 90
deg
Z2G resistive reach characteristic angle
75
Z2G-R.Reach
0.10 -
500.00
0.01 -
100.00
-
Z2G resistive reach
25.50
5.10
Z2G-DX.Angle
0 - 60
deg
Z2G directional-X characteristic angle
30
Z2G-DR.Angle
0 - 60
deg
Z2G directional-R characteristic angle (for
Quad)
5
I0K
Z2G-Krs
0 - 1000
%
Zero phase current factor, Self line R0/R1
100
Z2G-Kxs
0 - 1000
%
Zero phase current factor, Self line X0/X1
100
Z2G-Krm
0 - 1000
%
Zero phase current factor, Adjacent line
R0m/R1
0
Z2G-Kxm
0 - 1000
%
Zero phase current factor, Adjacent line
X0m/X1
0
TZ2G
0.00 - 100.00
s
Z2G operation delay time
0.30
Output
Z2G-EFL
Off / On
-
EFL operation condition used or not for Z2G
operation
On
Z2G-MPFBlk
Non / Block
-
Z2G operation block or not in multi phase fault
Non
Z2G-PSBBlk
Non / Block
-
Z2G operation block or not by PSB detection
Non
Z2G-LEBlk
Non / Block
-
Load encroachment enable
Non

Table of Contents