6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 166 -
ZG (Function ID 431001
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
Z4G-
Mho.Reach
0.10 -
500.00
0.01 -
100.00
-
Z4G mho reach (for Mho)
20.00
4.00
Z4G-MhoX.EN
Off / On
-
Z4G reactance reach use or not (for Mho)
Off
Z4G-X.Reach
0.10 -
500.00
0.01 -
100.00
-
Z4G reactance reach
20.00
4.00
Z4G-MhoR.EN
Off / On
-
Z4G resistive reach use or not (for Mho)
Off
Z4G-R.Angle
30 - 90
deg
Z4G resistive reach characteristic angle
75
Z4G-R.Reach
0.10 -
500.00
0.01 -
100.00
-
Z4G resistive reach
25.50
5.10
Z4G-
MhoDX.EN
Off / On
-
Z4G directional-X characteristic use or not (for
Mho)
Off
Z4G-DX.Angle
0 - 60
deg
Z4G directional-X characteristic angle
30
Quad
Z4G-X.Reach
0.10 -
500.00
0.01 -
100.00
-
Z4G reactance reach
20.00
4.00
Z4G-R.Angle
30 - 90
deg
Z4G resistive reach characteristic angle
75
Z4G-R.Reach
0.10 -
500.00
0.01 -
100.00
-
Z4G resistive reach
25.50
5.10
Z4G-DX.Angle
0 - 60
deg
Z4G directional-X characteristic angle
30
Z4G-DR.Angle
0 - 60
deg
Z4G directional-R characteristic angle (for
Quad)
5
I0K
Z4G-Krs
0 - 1000
%
Zero phase current factor, Self line R0/R1
100
Z4G-Kxs
0 - 1000
%
Zero phase current factor, Self line X0/X1
100
Z4G-Krm
0 - 1000
%
Zero phase current factor, Adjacent line
R0m/R1
0
Z4G-Kxm
0 - 1000
%
Zero phase current factor, Adjacent line
X0m/X1
0
Z4G-EFL
Off / On
-
EFL operation condition used or not for Z4G
operation
On
TZ4G
0.00 - 100.00
s
Z4G operation delay time
0.60
Output
Z4G-MPFBlk
Non / Block
-
Z4G operation block or not in multi phase fault
Non
Z4G-PSBBlk
Non / Block
-
Z4G operation block or not by PSB detection
Non
Z4G-LEBlk
Non / Block
-
Load encroachment enable
Non
Z4G-LPBlk
Non / Block
-
Z4G leading phase operation block
Non
Z4G-TPMD
1P / 3P
-
Z4G trip mode, phase segregated trip or 3-
phase trip
3P
Z4G-ARCBlk
Non / Block
-
Autoreclose execution block by Z4G-trip
Block
Z4G-OCFS-EN
Off / On
-
Fail-safe OC for Z4G-trip
Off
OCF4G
0.02 - 5.00
0.10 -
25.00
A
Fail-safe OC operation level for Z4G-trip
0.20
1.00
Z4G-SOTF
Off / On
-
SOTF using Z4G
Off
Z5G
Z5G-Dir
Forward / Reverse /
NonDir
-
Z5G direction to protect
Reverse
Mho
Z5G-Mho.Angle
30 - 90
deg
Z5G mho characteristic angle (for Mho)
85
Z5G-
Mho.Reach
0.10 -
500.00
0.01 -
100.00
-
Z5G mho reach (for Mho)
10.00
2.00
Z5G-MhoX.EN
Off / On
-
Z5G reactance reach use or not (for Mho)
Off
Z5G-X.Reach
0.10 -
500.00
0.01 -
100.00
-
Z5G reactance reach
10.00
2.00
Z5G-MhoR.EN
Off / On
-
Z5G resistive reach use or not (for Mho)
Off
Z5G-R.Angle
30 - 90
deg
Z5G resistive reach characteristic angle
75
Z5G-R.Reach
0.10 -
500.00
0.01 -
100.00
-
Z5G resistive reach
25.50
5.10
Z5G-
MhoDX.EN
Off / On
-
Z5G directional-X characteristic use or not (for
Mho)
Off