6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 167 -
ZG (Function ID 431001
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
Z5G-DX.Angle
0 - 60
deg
Z5G directional-X characteristic angle
30
Quad
Z5G-X.Reach
0.10 -
500.00
0.01 -
100.00
-
Z5G reactance reach
10.00
2.00
Z5G-
X.GrAngleEN
Off / On-Set / On-
Adapt
-
ZG gradient characteristic
Off
Z5G-R.Angle
30 - 90
deg
Z5G resistive reach characteristic angle
75
Z5G-R.Reach
0.10 -
500.00
0.01 -
100.00
-
Z5G resistive reach
25.50
5.10
Z5G-DX.Angle
0 - 60
deg
Z5G directional-X characteristic angle
30
Z5G-DR.Angle
0 - 60
deg
Z5G directional-R characteristic angle (for
Quad)
5
I0K
Z5G-Krs
0 - 1000
%
Zero phase current factor, Self line R0/R1
100
Z5G-Kxs
0 - 1000
%
Zero phase current factor, Self line X0/X1
100
Z5G-Krm
0 - 1000
%
Zero phase current factor, Adjacent line
R0m/R1
0
Z5G-Kxm
0 - 1000
%
Zero phase current factor, Adjacent line
X0m/X1
0
TZ5G
0.00 - 100.00
s
Z5G operation delay time
0.50
Z5G-CovCoeff
1.5 - 10.0
-
Covered characteristic size coefficient
1.5
Output
Z5G-EFL
Off / On
-
EFL operation condition used or not for Z5G
operation
On
Z5G-MPFBlk
Non / Block
-
Z5G operation block or not in multi phase fault
Non
Z5G-PSBBlk
Non / Block
-
Z5G operation block or not by PSB detection
Non
Z5G-LEBlk
Non / Block
-
Load encroachment enable
Non
Z5G-LPBlk
Non / Block
-
Z5G leading phase operation block
Non
Z5G-TPMD
1P / 3P
-
Z5G trip mode, phase segregated trip or 3-
phase trip
3P
Z5G-ARCBlk
Non / Block
-
Autoreclose execution block by Z5G-trip
Block
Z5G-OCFS-EN
Off / On
-
Fail-safe OC for Z5G-trip
Off
OCF5G
0.02 - 5.00
0.10 -
25.00
A
Fail-safe OC operation level for Z5G-trip
0.20
1.00
Z5G-SOTF
Off / On
-
SOTF using Z5G
Off
Z1XG
Z1XG-Dir
Forward / Reverse /
NonDir
-
Z1XG direction to protect
Forward
Mho
Z1XG-
Mho.Angle
30 - 90
deg
Z1XG mho characteristic angle (for Mho)
85
Z1XG-
Mho.Reach
0.10 -
500.00
0.01 -
100.00
-
Z1XG mho reach (for Mho)
12.00
2.40
Z1XG-
MhoX.EN
Off / On
-
Z1XG reactance reach use or not (for Mho)
Off
Z1XG-X.Reach
0.10 -
500.00
0.01 -
100.00
-
Z1XG reactance reach
12.00
2.40
Z1XG-
MhoR.EN
Off / On
-
Z1XG resistive reach use or not (for Mho)
Off
Z1XG-R.Angle
30 - 90
deg
Z1XG resistive reach characteristic angle
75
Z1XG-R.Reach
0.10 -
500.00
0.01 -
100.00
-
Z1XG resistive reach
25.50
5.10
Z1XG-
MhoDX.EN
Off / On
-
Z1XG directional-X characteristic use or not
(for Mho)
Off
Z1XG-
DX.Angle
0 - 60
deg
Z1XG directional-X characteristic angle
30
Quad
Z1XG-X.Reach
0.10 -
500.00
0.01 -
100.00
-
Z1XG reactance reach
12.00
2.40

Table of Contents