6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 168 -
ZG (Function ID 431001
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
Z1XG-
X.GrAngleEN
Off / On-Set / On-
Adapt
-
ZG gradient characteristic
Off
Z1XG-R.Angle
30 - 90
deg
Z1XG resistive reach characteristic angle
75
Z1XG-R.Reach
0.10 -
500.00
0.01 -
100.00
-
Z1XG resistive reach
25.50
5.10
Z1XG-
DX.Angle
0 - 60
deg
Z1XG directional-X characteristic angle
30
Z1XG-
DR.Angle
0 - 60
deg
Z1XG directional-R characteristic angle (for
Quad)
5
I0K
Z1XG-Krs
0 - 1000
%
Zero phase current factor, Self line R0/R1
100
Z1XG-Kxs
0 - 1000
%
Zero phase current factor, Self line X0/X1
100
Z1XG-Krm
0 - 1000
%
Zero phase current factor, Adjacent line
R0m/R1
0
Z1XG-Kxm
0 - 1000
%
Zero phase current factor, Adjacent line
X0m/X1
0
TZ1XG
0.00 - 100.00
s
Z1XG operation delay time
0.00
Z1XG-CovCoeff
1.5 - 10.0
-
Covered characteristic size coefficient
1.5
Output
Z1XG-EFL
Off / On
-
EFL operation condition used or not for Z1XG
operation
On
Z1XG-MPFBlk
Non / Block
-
Z1XG operation block or not in multi phase
fault
Block
Z1XG-PSBBlk
Non / Block
-
Z1XG operation block or not by PSB detection
Block
Z1XG-LEBlk
Non / Block
-
Load encroachment enable
Non
Z1XG-LPBlk
Non / Block
-
Z1XG leading phase operation block
Non
Z1XG-TPMD
1P / 3P
-
Z1XG trip mode, phase segregated trip or 3-
phase trip
1P
Z1XG-ARCBlk
Non / Block
-
Autoreclose execution block by Z1XG-trip
Non
Z1XG-OCFS-
EN
Off / On
-
Fail-safe OC for Z1XG-trip
Off
OCF1XG
0.02 - 5.00
0.10 -
25.00
A
Fail-safe OC operation level for Z1XG-trip
0.20
1.00
Z1XG-SOTF
Off / On
-
SOTF using Z1XG
Off
Note 1: On-Adapt is only applicable when Forward is set for ZG. If On-Adapt is set
for Reverse operation, it is necessary to set scheme switch [ZG-X.GrAngleEN]=Off.
Note 2: When On-Adapt is set for scheme switch [ZG-X.GrAngleEN], the setting
value [ZGF-X.GrAngle1] will be calculated by itself. However, the user should set
a value be set for [ZGF-X.GrAngle2] regardless of the setting of scheme switch
[ZG-X.GrAngleEN