EasyManua.ls Logo

Toshiba GR200 Series - Page 278

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 255 -
EF(Function ID:441001)
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
EF1-k
0.00000 - 500.00000
-
EF1 user original curve coefficient
0.00000
EF1-a
0.00000 - 10.00000
-
EF1 user original curve coefficient
0.00000
EF1-c
0.00000 - 10.00000
-
EF1 user original curve coefficient
0.00000
EF1-kr
0.00000 - 500.00000
-
EF1 user original curve coefficient
0.00000
EF1-b
0.00000 - 10.00000
-
EF1 user original curve coefficient
0.00000
Output
EF1-VTFBlk
Non / Block
-
EF1 operation block by VTF
Non
EF1-CTFBlk
Non / Block
-
EF1 operation block by CTF
Non
EF1-UseFor
Trip / Alarm
-
EF1 used for trip or alarm
Trip
EF1-ARCBlk
Non / Block
-
Autoreclose block by EF1
Block
EF2
EF2-Dir
NonDir / Forward /
Reverse
-
EF2 directional characteristic
NonDir
Fwd/
EF2-Angle
0 - 180
deg
EF2 directional characteristic angle
45
Rev
EF2-Vpol
0.5 - 100.0
V
EF2 polarizing voltage level
3.0
EF2-Timer
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
IEEE-MI / IEEE-VI /
IEEE-EI / US-CO2 /
US-CO8 / Original
-
EF2 delay type
DT
DT
EF2
0.02 -
50.00
0.10 -
250.00
A
EF2 threshold (in DT mode)
0.30
1.50
EF2-DPR
10 - 100
%
EF2 drop-out/pick-up ratio
100
TEF2
0.00 - 300.00
s
EF2 operating delay time (in DT mode)
1.00
IEC
EF2
0.02 -
5.00
0.10 -
25.00
A
EF2 threshold (in IDMT mode)
0.30
1.50
EF2-DPR
10 - 100
%
EF2 drop-out/pick-up ratio
100
EF2-TMS-IEC
0.010 - 50.000
-
EF2 time multiplier of IEC inverse curve
1.000
TEF2R
0.00 - 300.00
s
EF2 definite time reset delay
0.00
UK
EF2
0.02 -
5.00
0.10 -
25.00
A
EF2 threshold (in IDMT mode)
0.30
1.50
EF2-DPR
10 - 100
%
EF2 drop-out/pick-up ratio
100
EF2-TMS-UK
0.010 - 50.000
-
EF2 time multiplier of UK inverse curve
1.000
TEF2R
0.00 - 300.00
s
EF2 definite time reset delay
0.00
IEEE
EF2
0.02 -
5.00
0.10 -
25.00
A
EF2 threshold (in IDMT mode)
0.30
1.50
EF2-DPR
10 - 100
%
EF2 drop-out/pick-up ratio
100
EF2-TMS-
IEEE
0.010 - 50.000
-
EF2 time multiplier of IEEE inverse curve
1.000
EF2-Rtimer
DEF / DEP
-
EF2 reset delay type of IEEE
DEF
TEF2R
0.00 - 300.00
s
EF2 definite time reset delay
0.00
EF2-RTMS-
IEEE
0.010 - 50.000
-
EF2 dependent reset time multiplier of IEEE
inverse curve
1.000
US
EF2
0.02 -
5.00
0.10 -
25.00
A
EF2 threshold (in IDMT mode)
0.30
1.50
EF2-DPR
10 - 100
%
EF2 drop-out/pick-up ratio
100
EF2-TMS-US
0.010 - 50.000
-
EF2 time multiplier of US inverse curve
1.000
EF4-Rtimer
DEF / DEP
-
EF2 reset delay type of US
DEF
TEF2R
0.00 - 300.00
s
EF2 definite time reset delay
0.00
EF2-RTMS-US
0.010 - 50.000
-
EF2 dependent reset time multiplier of US
inverse curve
1.000
ORG
EF2
0.02 -
5.00
0.10 -
25.00
A
EF2 threshold (in IDMT mode)
0.30
1.50
EF2-DPR
10 - 100
%
EF2 drop-out/pick-up ratio
100
EF2-TMS-ORG
0.010 - 50.000
-
EF2 time multiplier of Original inverse curve
1.000

Table of Contents