- 289 -
2.19.4 Scheme logic
Figure 2.19-3 shows the scheme logic for the BCD function. The BCD function issues a trip
signal through a delayed pick-up timer, the value of which is set for [TBCD]. The operation of
the BCD function can be disabled using scheme switch [BCD-EN] Off.
Figure 2.19-3 Broken conductor protection scheme logic
Normal power system levels of negative phase sequence restrict the setting value of
[BCD]. The BCD function continuously determines the ratio (I
2F
/I
1F
). User can check the
present ratio along with the maximum value (I
21
max) that has been examined for 15 minutes
ago. We recommend that user should distinguish the present ratio against the value on
commissioning stage; and user should set a value for [BCD] from 130% to 150% of the ratio has
been checked.
Note: The ratio (I
2F
/ I
1F
) is displayed only when the current in positive-sequence (or load
current) on the secondary circuit is larger than 2% of the rated current on
secondary circuit.
2.19.5 Setting
Setting of BCD(Function ID: 452001)
BCD protection scheme switch
BCD relay operating value (I2/I1)
BCD operation block by 2f-detection
BCD operation block by CTF
BCD used for trip or alarm