6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 329 -
2.24.5 Setting
UV(Function ID: 470101)
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
BLK
UVBLK
Off / On
-
Operation canceled when UVBLK operated
Off
UVBLK
10.0
V
Threshold of UVBLK element
10.0
TUVBLK
10.00
S
UVBLK operation delay timer
10.00
UV1-EN
Off / On
-
UV1 protection scheme switch
Off
UV2-EN
Off / On
-
UV2 protection scheme switch
Off
UV1
UV1-Timer
DT / IDMT / Original
-
UV1 delay type
DT
DT
UV1
5.0 - 130.0
V
UV1 threshold
60.0
UV1-DPR
100 - 120
%
UV1 drop-out/pick-up ratio
100
TUV1
0.00 - 300.00
s
UV1 operating delay time (in DT mode)
1.00
IDMT
UV1
5.0 - 130.0
V
UV1 threshold
60.0
UV1-DPR
100 - 120
%
UV1 drop-out/pick-up ratio
100
UV1-TMS
0.010 - 100.000
-
UV1 time multiplier (in IDMT mode)
1.000
TUV1R
0.0 - 300.0
s
UV1 definite time reset delay
0.0
ORG
UV1
5.0 - 130.0
V
UV1 threshold
60.0
UV1-DPR
100 - 120
%
UV1 drop-out/pick-up ratio
100
UV1-TMS
0.010 - 100.000
-
UV1 time multiplier (in ORG mode)
1.000
TUV1R
0.0 - 300.0
s
UV1 definite time reset delay
0.0
Output
UV1-VTFBlk
Non / Block
-
UV1 operation block by VTF
Non
UV1-UseFor
Trip / Alarm
-
UV1 used for trip or alarm
Trip
UV2
UV2-Timer
DT / IDMT / Original
-
UV2 delay type
DT
DT
UV2
5.0 - 130.0
V
UV2 threshold
60.0
UV2-DPR
100 - 120
%
UV2 drop-out/pick-up ratio
100
TUV2
0.00 - 300.00
s
UV2 operating delay time (in DT mode)
1.00
IDMT
UV2
5.0 - 130.0
V
UV2 threshold
60.0
UV2-DPR
100 - 120
%
UV2 drop-out/pick-up ratio
100
UV2-TMS
0.010 - 100.000
-
UV2 time multiplier (in IDMT mode)
1.000
TUV2R
0.0 - 300.0
s
UV2 definite time reset delay
0.0
ORG
UV2
5.0 - 130.0
V
UV2 threshold
60.0
UV2-DPR
100 - 120
%
UV2 drop-out/pick-up ratio
100
UV2-TMS
0.010 - 100.000
-
UV2 time multiplier (in ORG mode)
1.000
TUV2R
0.0 - 300.0
s
UV2 definite time reset delay
0.0
Output
UV2-VTFBlk
Non / Block
-
UV2 operation block by VTF
Non
UV2-UseFor
Trip / Alarm
-
UV2 used for trip or alarm
Trip
Test tool(Function ID: 470101)
Setting device
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
Function test
UV-Test
Off / On
-
Not to execute UVBLK element
Off