6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 345 -
2.26.3 Setting
FRQ(Function ID: 475001)
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
FRQ-EN
Off / On
-
FRQ protection enable
Off
FRQ
FRQBLK
40.0 - 100.0
V
Threshold to cancel FRQ operations
40.0
FRQ1-EN
Off / On
-
FRQ1 protection enable
Off
FRQ2-EN
Off / On
-
FRQ2 protection enable
Off
FRQ3-EN
Off / On
-
FRQ3 protection enable
Off
FRQ4-EN
Off / On
-
FRQ4 protection enable
Off
FRQ5-EN
Off / On
-
FRQ5 protection enable
Off
FRQ6-EN
Off / On
-
FRQ6 protection enable
Off
DFRQ1-EN
Off / On
-
DFRQ1 protection enable
Off
DFRQ2-EN
Off / On
-
DFRQ2 protection enable
Off
DFRQ3-EN
Off / On
-
DFRQ3 protection enable
Off
DFRQ4-EN
Off / On
-
DFRQ4 protection enable
Off
DFRQ5-EN
Off / On
-
DFRQ5 protection enable
Off
DFRQ6-EN
Off / On
-
DFRQ6 protection enable
Off
FRQ1
FRQ1-Chara
OverFrq / UnderFrq
-
The selection of FRQ1 character
UnderFrq
FRQ1
-10.00 - 10.00
Hz
FRQ1 threshold
-1.00
TFRQ1
0.00 - 300.00
s
FRQ1 operating delay time
1.00
Output
FRQ1-UseFor
Trip / Alarm
-
FRQ1 used for trip or alarm
Trip
FRQ2
FRQ2-Chara
OverFrq / UnderFrq
-
The selection of FRQ2 character
UnderFrq
FRQ2
-10.00 - 10.00
Hz
FRQ2 threshold
-1.00
TFRQ2
0.00 - 300.00
s
FRQ2 operating delay time
1.00
Output
FRQ2-UseFor
Trip / Alarm
-
FRQ2 used for trip or alarm
Trip
FRQ3
FRQ3-Chara
OverFrq / UnderFrq
-
The selection of FRQ3 character
UnderFrq
FRQ3
-10.00 - 10.00
Hz
FRQ3 threshold
-1.00
TFRQ3
0.00 - 300.00
s
FRQ3 operating delay time
1.00
Output
FRQ3-UseFor
Trip / Alarm
-
FRQ3 used for trip or alarm
Trip
FRQ4
FRQ4-Chara
OverFrq / UnderFrq
-
The selection of FRQ4 character
UnderFrq
FRQ4
-10.00 - 10.00
Hz
FRQ4 threshold
-1.00
TFRQ4
0.00 - 300.00
s
FRQ4 operating delay time
1.00
Output
FRQ4-UseFor
Trip / Alarm
-
FRQ4 used for trip or alarm
Trip
FRQ5
FRQ5-Chara
OverFrq / UnderFrq
-
The selection of FRQ5 character
UnderFrq
FRQ5
-10.00 - 10.00
Hz
FRQ5 threshold
-1.00
TFRQ5
0.00 - 300.00
s
FRQ5 operating delay time
1.00
Output
FRQ5-UseFor
Trip / Alarm
-
FRQ5 used for trip or alarm
Trip
FRQ6
FRQ6-Chara
OverFrq / UnderFrq
-
The selection of FRQ6 character
UnderFrq
FRQ6
-10.00 - 10.00
Hz
FRQ6 threshold
-1.00
TFRQ6
0.00 - 300.00
s
FRQ6 operating delay time
1.00
Output
FRQ6-UseFor
Trip / Alarm
-
FRQ6 used for trip or alarm
Trip
DFRQ1
DFRQ1-Chara
Rise / Down
-
The selection of DFRQ1 character
Down
DFRQ1
0.1 - 15.0
Hz/s
DFRQ1 threshold
0.5
Output
DFRQ1-UseFor
Trip / Alarm
-
DFRQ1 used for trip or alarm
Trip
DFRQ2
DFRQ2-Chara
Rise / Down
-
The selection of DFRQ2 character
Down
DFRQ2
0.1 - 15.0
Hz/s
DFRQ2 threshold
0.5
Output
DFRQ2-UseFor
Trip / Alarm
-
DFRQ2 used for trip or alarm
Trip
DFRQ3
DFRQ3-Chara
Rise / Down
-
The selection of DFRQ3 character
Down
DFRQ3
0.1 - 15.0
Hz/s
DFRQ3 threshold
0.5
Output
DFRQ3-UseFor
Trip / Alarm
-
DFRQ3 used for trip or alarm
Trip
DFRQ4
DFRQ4-Chara
Rise / Down
-
The selection of DFRQ4 character
Down
DFRQ4
0.1 - 15.0
Hz/s
DFRQ4 threshold
0.5
Output
DFRQ4-UseFor
Trip / Alarm
-
DFRQ4 used for trip or alarm
Trip
DFRQ5
DFRQ5-Chara
Rise / Down
-
The selection of DFRQ5 character
Down
DFRQ5
0.1 - 15.0
Hz/s
DFRQ5 threshold
0.5

Table of Contents