EasyManua.ls Logo

Toshiba GR200 Series - (iv) Calculation error; 2.32.3 Selection of calculation results

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 392 -
(iv) Calculation error
User should note that the calculation error could be larger when a setting value is far from
actual line impedance. For example, if abnormal settings
1
are done, the calculation error will
be appeared notably.
The calculation error can be with in ± 2.5 km when the following conditions are applied:
A fault is assumed to arise up to 100 km distance.
The fault current is larger than double of the rated current
2
(
).
The reactance
3
per unit length (

) is longer than a value (

).
In other words, this calculation error can be with in ±2.5% when the following conditions
are applied:
The line length (L) is shorter than 100km.
The reactance per unit length (

) is larger than a value (

).
The fault current is larger than double of the rated current
2
(
).
1
Note: Abnormal settings can be exist when values are far from actual impedance data of
transmission line. For example, resistance value is so larger then reactance value,
and so on.
2
Note: Rated current (In) is described separately. (See Chapter
Technical description:
Transformer module
)
3
Note: The term X1 is the reactance component of line impedance.
2.32.3 Selection of calculation results
At the outset, we discuss that the FL calculation consist of two groups: (1) FL calculation with
data at a local-terminal and remote-terminals and (2) FL calculation with data at a local-
terminal only. Hence, either (1) or (2) is selected as a calculation result in accordance with a
fault condition. The FL selects the result of (2) FL calculation with data at a local-terminal
only when the FL finds the following conditions after the calculations:
The calculation results are less than 20% of the line length (L).
The result difference between (1) and (2) is within 5% of the line length (L).
The calculation result is less than 40km.

Table of Contents

Related product manuals