- 408 -
2.33.1 Command for tripping CB and signal to block reclosing CB#1/CB#2
The TRC logic is designed to issue per-phase trip or three-phase trip commands when a fault
occurs. Table 2.33-2 shows the receipt of trip signals from the protection functions, which are
identified by ‘Protection function identification numbers (‘
*
’). Note that an operation block
signal for the ARC function is also provided along with the trip signal.
Table 2.33-2 Trip/ARC block signal inputs to the TRC function
Trip and ARC-block signals provided by the protection functions
Note: ‘N.A.’ represents ‘Not available for the IED’, ‘X’ represents a ‘Valid signal received
from the protection function’, ‘–’ represents that no ‘valid signal’ received in the