- 421 -
2.34.1 Overview
Table 2.34-2 summarizes the reclosing operations and the modes in the ARC function. The
ARC function can operate for both a single CB arrangement and double CBs (1.5CB)
arrangement; hence, the ARC function is grouped into two logics: ARC1 for CB#1 and ARC2
for CB#2. Note that multi-shots scheme is only available for 1CB arrangement (CB#1). The
‘ORIGINAL’ is provided for the user’s programing.
Table 2.34-2 ARC operation modes and shot numbers
ARC1 SHOT1
or/and
ARC2 SHOT
x: Operation is applicable N.A: Operation is not applicable
(i) Breaker system
The ARC function can operate in several breaker systems, as shown in Figure 2.34-1. For the
1.5CB arrangement, the ARC1 and ARC2 logics operate separately; the user can select
different reclosing scheme (Figure 2.34-1.b). In parallel lines, the ARC function can take
several reclosing schemes when the communication application (COMM_APPL) is available
(Figure 2.34-1.c).