(iv) MPAR mode
Figure 2.34-5 illustrates the ARC function when settings of are performed in both Table 2.34-9
and Table 2.34-10.
Table 2.34-9 Block parts in MPAR mode
Corresponding logics
Detailed logic
ARC1-Mode input
Figure 2.34-11
Shot number
Figure 2.34-13
Link judgment
Figure 2.34-28
Start
Figure 2.34-14
Initiation
Figure 2.34-15
Shot counter
Figure 2.34-16
ARC1 MPAR
Figure 2.34-27
ARC1 SHOT2
Figure 2.34-21
Issuing
Figure 2.34-22
Success check
Figure 2.34-23
Reclose sequence
Figure 2.34-24
Table 2.34-10 Setting examples in MPAR mode
Categories
Items
Settings
Corresponding logics
ARC general
ARC1-EN
On
ARC1-MODE
MPAR
Figure 2.34-11
ARC2-EN
Off
ARC2-MOED
Off
Figure 2.34-12
MPAR-MODE
M2
Table 2.34-13
ARC-ORDER
CB1
Figure 2.34-24
MultiShot-EN
On
ARC-NUM
S2
Figure 2.34-13
ARC1
TREADY
60.0s
Figure 2.34-15
TSPAR1
0.80s
Figure 2.34-18
TSPAR1_SUB
300.00s
Figure 2.34-18
TTPAR1
0.60s
Figure 2.34-20
TTPAR1_SUB
300.00s
Figure 2.34-20
TMPAR1
1.00s
Figure 2.34-27
TMPAR1_SUB
300.00s
Figure 2.34-27
TRR1
2.00s
Figure 2.34-20
TCCW1
0.20s
Figure 2.34-22
ARC1 multi-shot
TD_MS2
20.00s
Figure 2.34-21
TRR_MS2
30.00s
Figure 2.34-21
ARC misc.
ARC-SucChk
On
Figure 2.34-23
TARCSUC
0.30s
Figure 2.34-23
FT-3pFault
Off
Figure 2.34-14
TRESET
0.30s
Figure 2.34-15
TEVLV
0.30s
Figure 2.34-17
SHOTNUM-TEST
Off
Figure 2.34-16
PROT-COMMON
CB-System
1CB
See Protection common function
VCHK
ARC1-VCHK EN
On
See Voltage check for autoreclose
TRC
TP-MODE
Per-Phase
See Trip circuit

Table of Contents