6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 463 -
Settings [ARC-MANOLK]=FT/TPAR/SPAR&TPAR in [MPAR-MODE]=M2
Table 2.34-13 shows tripping and reclosing results when the setting [MPAR-MODE] is M2 (i.e.,
M2 means that two or three unfaulted (healthy) phases exist in the parallel lines; respective
unfualted phases are different).
For setting [ARC-MANOLK]=TPAR or SPAR&TPAR, the CB can be reclosed in the TPAR
scheme when the MPAR-LINK condition is not observed.
For setting [ARC-MANOLK]=FT, the ARC function abandons to reclose the CB as when
the MPAR-LINK condition is not achieved in the paralleled lines.
Table 2.34-13 Tripped phases and mode for CB reclosing in [MPAR-MODE]=M2
TRC tripping with [TP-MODE]=PER-PHASE ARC reclosing mode with setting [MPAR-MODE]=M2
No
Faulted phases
Setting [ARC-MANOLK]
Line RQ
Line ST
FT
TPAR
SPAR&TPAR
A
B
C
A
B
C
Line RQ
Line ST
Line RQ
Line ST
Line RQ
Line ST
1
x
1ΦTMPAR
1ΦTMPAR
1ΦTMPAR
2
x
x
2ΦTFT
2ΦTTPAR
2ΦTTPAR
3
x
x
x
3ΦTFT
3ΦTTPAR
3ΦTTPAR
4
x
1ΦTMPAR
(N/A)
1ΦTMPAR
(N/A)
1ΦTMPAR
(N/A)
5
x
x
1ΦTMPAR
1ΦTMPAR
1ΦTMPAR
1ΦTMPAR
1ΦTMPAR
1ΦTMPAR
6
x
x
2ΦTMPAR
(N/A)
2ΦTMPAR
(N/A)
2ΦTMPAR
(N/A)
7
x
x
1ΦTMPAR
1ΦTMPAR
1ΦTMPAR
1ΦTMPAR
1ΦTMPAR
1ΦTMPAR
8
x
x
x
2ΦTMPAR
1ΦTMPAR
2ΦTMPAR
1ΦTMPAR
2ΦTMPAR
1ΦTMPAR
9
x
x
x
x
2ΦTFT
2ΦTFT
2ΦTTPAR
2ΦTTPAR
2ΦTTPAR
2ΦTTPAR
10
x
x
x
3ΦTMPAR
(N/A)
3ΦTMPAR
(N/A)
3ΦTMPAR
(N/A)
11
x
x
x
2ΦTMPAR
1ΦTMPAR
2ΦTMPAR
1ΦTMPAR
2ΦTMPAR
1ΦTMPAR
12
x
x
x
x
2ΦTMPAR
2ΦTMPAR
2ΦTMPAR
2ΦTMPAR
2ΦTMPAR
2ΦTMPAR
13
x
x
x
x
3ΦTMPAR
1ΦTMPAR
3ΦTMPAR
1ΦTMPAR
3ΦTMPAR
1ΦTTPAR
14
x
x
x
x
x
3ΦTFT
2ΦTFT
3ΦTTPAR
2ΦTTPAR
3ΦTTPAR
2ΦTTPAR
15
x
x
x
x
x
x
3ΦTFT
3ΦTFT
3ΦTTPAR
3ΦTTPAR
3ΦTTPAR
3ΦTTPAR
x: Occurrence of the fault
: Not energized (out of service)
MPAR: To issue a reclose command by ARC_MPAR_COND
TPAR: The TPAR scheme issuing three-phases tripping by ARC_TPAR_COND; then, to
issue a reclose command
FT: To abandon reclosing CB after ARC issuing three-phases tripping by FT setting
1ΦT: To issue a single-phase tripping
2ΦT: To issue two-phases tripping
3ΦT: To issue three-phases tripping
(N.A): Tripping and reclosing do not perform