EasyManua.ls Logo

Toshiba GR200 Series - 2.35.4 VCHK1 setting for 1 CB system

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 483 -
2.35.4 VCHK1 setting for 1CB system
When the VCHK1 is applied to 1CB system, OVB and UVB check the voltage of a Bus-bar,
whereas OVL and UVL check the voltage of Line, as described earlier. The Bus-bar and Line
voltages are obtained in the VCT
1
. Thus, user should set the scheme switches [SYN-VBus] and
[SYN-VLine] in accordance with the phase(s) of input-voltage(s). The following are the setting
examples when VCHK is used in 1CB system.
1
Note: For more information on VCT, see
Chapter Technical description: Transfer
module
. For external connection, see
Appendix: Typical external connection
.
Table 2.35-6 VCHK line selection setting
Scheme switch
Set
Comment
SYN-VBus
V-L1 / V-L2 / V-L3
V-L12 / V-L23 / V-L31
V2-L1 / V2-L2 / V2-L3
V2-L12 / V2-L23 / V2-L31
V3 / V4
Selection of Bus
voltage(Running Voltage) for
SYN1
SYN-VLine
V-L1 / V-L2 / V-L3
V-L12 / V-L23 / V-L31
V2-L1 / V2-L2 / V2-L3
V2-L12 / V2-L23 / V2-L31
V3 / V4
Selection of Line voltage
(Incoming Voltage) for SYN1

Table of Contents

Related product manuals