EasyManua.ls Logo

Toshiba GR200 Series - (ii) Setting example 2 (Bus-bar VT=three phases, Line VT=phase-BC)

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 485 -
(ii) Setting example 2 (Bus-bar VT=three phases, Line VT=phase-BC)
VCT
V
a
V
c
Vs
V
b
Line VT
(Phase B-C)
Bus-bar VT
(Three Phase)
V
bc
Line
Bus-bar
a. Phasor diagram in Bus-bar
b. Phasor diagram in Line
V
a
(V
L1
)
V
b
(V
L2
)
V
c
(V
L3
)
Vs (V
3
)
Vs2 (V4)
V
Bus-bar
(V
bc
)
2
V
Line
(Vs)
1
Figure 2.35-7 Example 2: Input voltages and respective phasor diagram for SYN1
1
Note: V
Bus-bar
is Running voltage.
2
Note: V
Line
is Incoming voltage.
Similarly, Figure 2.35-7 shows the VCT input voltages and phases from Bus-bar and Line.
In this case, configure the settings in accordance with Figure 2.35-7 and Table 2.35-8.
Table 2.35-8 Setting for example 2
Output voltage at VT
Bus-bar VT= Three phase
Line VT= Phase-BC
Input voltage at VCHK
Running voltage(V
b and c
)= Phase-B and C (Bus-bar VT)
Incoming voltage (Vs)= Phase-BC (Line VT)
VCHK Setting
3
[SYN-VBus] = V-L23
[SYN-VLine]= V3
3
Note: V3 is set for the scheme switch [SYN-VLine]. This is because the resultant phase
of V-L2, V-L3
and V3 is same.

Table of Contents

Related product manuals