2.35.7 Setting
VCHK(Function ID: 4A8001) at Autoreclose
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
ARC1-VCHK-
EN
Off / On
-
VCHK1 scheme switch
Off
ARC2-VCHK-
EN
Off / On
-
VCHK2 scheme switch
Off
ARC1
Voltage
check
SYN-Vbus
V-L1 / V-L2 / V-L3 / V-
L12 / V-L23 / V-L31 /
V2-L1 / V2-L2 / V2-L3
/ V2-L12 / V2-L23 /
V2-L31 / V3 / V4
-
Running Voltage
V3
SYN-Vline
V-L1 / V-L2 / V-L3 / V-
L12 / V-L23 / V-L31 /
V2-L1 / V2-L2 / V2-L3
/ V2-L12 / V2-L23 /
V2-L31 / V3 / V4
-
Incoming Voltage
V-L1
VCHK-OVB
10 - 150
V
Voltage for the checking Live-Bus
51
VCHK-UVB
10 - 150
V
Voltage for the checking Dead-Bus
13
VCHK-OVL
10 - 150
V
Voltage for the checking Live-Line
51
VCHK-UVL
10 - 150
V
Voltage for the checking Dead-Line
13
SYN1-Angle
0 - 75
deg
Difference angle for the checking SYN1
30
SYN1-dV
0 - 150
V
Difference voltage for the checking SYN1
150
SYN1-df
0.01 - 2.00
Hz
Difference frequency for the checking SYN1
1.00
ARC1-LB_DL
Off / On
-
Voltage check Live-Bus & Dead-Line is
applied to ARC1
Off
ARC1-DB_LL
Off / On
-
Voltage check Dead-Bus & Live-Line is
applied to ARC1
Off
ARC1-DB_DL
Off / On
-
Voltage check Dead-Bus & Dead-Line is
applied to ARC1
Off
ARC1-SYN1
Off / On
-
Voltage check SYN1 is applied to ARC1
Off
ARC1-
NOVCHK
Off / On
-
Voltage check is not applied to ARC1
On
T_LB_DL
0.01 - 100.00
s
Voltage check time Live-Bus and Dead-Line
0.05
T_DB_LL
0.01 - 100.00
s
Voltage check time Dead-Bus and Live-Line
0.05
T_DB_DL
0.01 - 100.00
s
Voltage check time Dead-Bus and Dead-Line
0.05
T_SYN1
0.01 - 100.00
s
Voltage check time SYN1
1.00
T_OVL3P
0.01 - 100.00
s
Voltage check time 3phase Live-line
0.05
ARC2
Voltage
check
SYN-Vline2
V-L1 / V-L2 / V-L3 / V-
L12 / V-L23 / V-L31 /
V2-L1 / V2-L2 / V2-L3
/ V2-L12 / V2-L23 /
V2-L31 / V3 / V4
-
Running Voltage
V4
VCHK-OVL2
10 - 150
V
Voltage for the checking Live-Line2
51
VCHK-UVL2
10 - 150
V
Voltage for the checking Dead-Line2
13
SYN2-Angle
0 - 75
deg
Difference angle for the checking SYN2
30
SYN2-dV
0 - 150
V
Difference voltage for the checking SYN2
150
SYN2-df
0.01 - 2.00
Hz
Difference frequency for the checking SYN2
1.00
ARC2-LL2_DL
Off / On
-
Voltage check Live-Line2 & Dead-Line is
applied to ARC2
Off
ARC2-DL2_LL
Off / On
-
Voltage check Dead-Line2 & Live-Line is
applied to ARC2
Off
ARC2-DL2_DL
Off / On
-
Voltage check Dead-Line2 & Dead-Line is
applied to ARC2
Off
ARC2-SYN2
Off / On
-
Voltage check SYN2 is applied to ARC2
Off