EasyManua.ls Logo

Toshiba GR200 Series - 2.36 Transmission control function (DIF_COMM)

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 494 -
Transmission control function (DIF_COMM)
In order that several protection functions can handle their computation diversely, the
transmission control (DIF_COMM) function is provided along with protection signalling
modules. The DIF_COMM function operates with the telecommunication system; the
telecommunication medium is provided such as dark fiber (dedicated fiber-optic cable),
multiplexed fiber-optics, digital microwave, and others. Accordingly, the protection functions
linked with the remote-terminals can exchange their data mutually.
For the DIF_COMM operation, the user should arrange communication interface,
synchronization method, and topology consideration: the communication interface provides the
link means physically; the synchronization method provides accuracy in their computation;
the topology provides the network configuration philosophy
Note: For more information about the protection signaling modules, see Chapter
Technical description: Signal processing module: Communication modules
. .
─────────────────────────────────────────────────────────────────
Note: The implementation of such features is dependent upon the selection of hardware and
the configuration of functions. Several IED models do not support certain features. To
determine whether a particular feature has been implemented within an IED, identify the IED
ordering number; and check the order number at the G&T position” referring to the
comparison table below. For more information, see
Appendix: Ordering
.
Table 2.36-1 Comparative table in respective ordering numbers
Features
Ordering No. at G&T
33
37
Main features
Communication for protection
Number of terminals
Available maximum terminals
3
3
Number of channels
Maximum channel number per IED
2
2
: Applicable NA: Not applicable