6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 581 -
Note: Although the LED_RST_COM signal is connected previously with several LEDs,
by the manufacturer, user can also connect the signal with the LEDs. See section
3.6.4 for how to connect.
(iii) Operate condition
Figure 3.6-8 shows the operate condition logic of the LEDR function, which is used to determine
a reset-condition for the operation.
Operate condition
LEDR function (Function ID: 528001)
To operate logic
Control hierarchy (e.g. 43RL) (PLC connection point) *5
IED serious error detected
[LEDDR1_EN]
On
Users must setup this condition correctly
Function Automatic sequence control is in progress
S4301_STATE
Command blocking*1 (S4301 defines ”Blocked”)
Double Command Blocking detected*2
Other devices traveling detected*3
DCB RCV OR
Traveling OR
ASEQ_MULTI_SEL
LEDR01_CTRL_RIGHT
528001 820701ED50
SERI_ERR
&
&
1
Unmatched condition detected *4
Figure 3.6-8 Operate condition logic in LEDR
*6
*1
Note: Command blocking disables all operation except for its own: the command
blocking function is initiated by the status of S4301 in a software controller
(SOFTSW). The IEC 61850 standard defines the command blocking function as
CmdBlk. For more information on S4301, see Chapter
Control and monitoring
application: Software switch control function
. See the signal S4301_STATE of
Table 3.6-2.
*2
Note: “Double Command Blocking (DCB) is an operation philosophy in the
common control function (CMNCTRL). It can be used to protect the substation.
The user can program it using GR-TIEMS. The DCB operating signal is denoted
as “DCB RCV_OR in Table 3.6-2. For more information, see Chapter
Control and
monitoring application: Common controls
.
*3
Note: If the event “device-travelling” is detected in the CMNCTRL function, it
indicates that another operator is changing the status of a device. Thus, the IED
should inhibit the operation of any device for the duration that the event is
detected. The detecting signal is denoted as “Traveling OR in Table 3.6-2.
*4
Note: Criteria “unmatched conditions” are decided when the “Test-bit status” in a
command is not identical to the “IED test status”.
*5
Note: The user must program the PLC logic for Control hierarchy condition”. The
user must connect that to the select condition logic using the connection point
LEDR01_CTRL_RIGHT. For more information, see chapter
Control and