6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 585 -
are required to be mapped for IEC 61850 communication
Table 3.6-5 Mapping signals for SPC object
Object_reference
Attribute
Type
FC
Signal Number
Signal Name
Ctrl/LLN0$LEDRs$origin
orCat
orCategory
ST
5280013107011008
LEDR01_ORCAT
Ctrl/LLN0$LEDRs$origin
orIdent
Octet64
ST
5280016A07011009
LEDR01_ORIDENT
Ctrl/LLN0$LEDRs
stVal
BOOLEAN
ST
5280013107011EA1
LED_RST_CMD
Ctrl/LLN0$LEDRs
q
Quality
ST
3010013110041005
Qual_Val
Ctrl/LLN0$LEDRs
t
Timestamp
ST
2003019010001006
SYS_TIME
Ctrl/LLN0$LEDRs
stSeld
BOOLEAN
ST
5280010007011001
LEDR01_STSELD
Note: Status (ST) is defined in the function constraint (FC) of the IEC 61850.
Figure 3.6-13 orCat attribute mapped for LEDRs object of LLN0
(iii) Mapping input data
The LEDR function can receive three commands select, operate, and cancel. Thus, the user
should map the input-point LED01_CONTROL_REQ to the IEC61850 communication. Table
3.6-6 shows the input-point LED01_CONTROL_REQ and the Object reference
Ctrl/LLN0$LEDRs; the user should map the input-point to the Object references having
attributes CO and CF. Figure 3.6-14 shows how to map a signal.
Note: The attribute is defined in the IEC 61850; CO stands for Control and CF
stands for Configuration in the functional constraint (FC).