- 595 -
(iii) Signal name and number
Note: The user should note the following descriptions shown in the column M/O for
each table:
“O” indicates that the signal is provided for optional use.
M indicates that the user should map/set/configure the signal; otherwise, the
user may experience an operational failure if the default settings are
used.
N/A indicates that the user cannot change the state of the signal.
Table 3.7-2 Mapping points for the reception of control command
Signal Number
Signal Name
Description
M/O
540001 700E016D09
GCNT01_CMM_REQ
GCNT01 control request(Mapping data)
M
540001 700E026D09
GCNT02_CMM_REQ
GCNT02 control request(Mapping data)
M
540001 700E036D09
GCNT03_CMM_REQ
GCNT03 control request(Mapping data)
M
540001 700E206D09
GCNT32_CMM_REQ
GCNT32 control request(Mapping data)
M
Table 3.7-3 Input signals to condition logic
Signal Number
Signal Name
Description
M/O
522001 000A011001
S4301_STATE
Command Blocking status ( Off / Blocked)
N/A
523001 000D001F40
ASEQ_MULTI_SEL
Automatic sequence control is in progress.
N/A
5A0001 0008001F41
DCB RCV OR
Double Command Blocking(DCB) is in progress.
N/A
5A0001 0008001F40
Traveling OR
Travelling events are detected.
N/A
5A0101 3100001F43
SERI_ERR
Serious Error detected
N/A
Table 3.7-4 PLC Connection point (Input signals from the control hierarchy logic)
Signal Number
Signal Name
Description
M/O
540001 800E00ED5A
GCNT00IN_TMP_51
Control hierarchy for GCNT0132
M
Table 3.7-5 PLC Monitoring points (Signal “select complete/ failed for BIO)
Signal Number
Signal Name
Description
540001 8A0E011E76
GCNT01_SLD_CSCN
GCNT01 Selection completed (Mapping)
540001 8A0E021E76
GCNT02_SLD_CSCN
GCNT02 Selection completed (Mapping)
540001 8A0E031E76
GCNT03_SLD_CSCN
GCNT03 Selection completed (Mapping)
540001 8A0E201E76
GCNT32_SLD_CSCN
GCNT32 Selection completed (Mapping)
5400018B0E011E7B
GCNT01_SLF_CSCN
GCNT01 select failed
5400018B0E021E7B
GCNT02_SLF_CSCN
GCNT02 select failed
5400018B0E031E7B
GCNT03_SLF_CSCN
GCNT03 select failed
.
5400018B0E201E7B
GCNT32_SLF_CSCN
GCNT32 select failed
Table 3.7-6 PLC Monitoring points (Signal “stSeld” for BIO)
Signal Number
Signal Name
Description
540001 000E011D91
GCNT01_TMP_01
GCNT01 count change selected signal(stSeld) for SAS
540001 000E021D91
GCNT02_TMP_01
GCNT02 count change selected signal(stSeld) for SAS
540001 000E031D91
GCNT03_TMP_01
GCNT03 count change selected signal(stSeld) for SAS