6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 604 -
(ii) Mapping output data
The user should group the GCNT01 signals with regard to GOOSE and REPORT; the user
should map them for IEC61850 communication using GR-TIEMS (Figure 3.7-18 illustrates
how to map a signal); it indicates that the signals for the GCNT01 function are required to
map the IEC 61850 communications.
Table 3.7-10 Mapping signals required for GIGO3302 object in GCNT01 function
Object_reference
Attribute
Type
FC
Signal Number
Signal Name
Ctrl/GGIO3302$ISCSO$origin
orCat
orCategory
ST
540001300e011D23
GCNT01_CNT_ORCAT
Ctrl/GGIO3302$ISCSO$origin
orIdent
Octet64
ST
5400016A0e011FA7
GCNT01_CNT_ORIDENT
Ctrl/GGIO3302$ISCSO
stVal
INT32
ST
540001320e011D20
GCNT01_CNT_VAL
Ctrl/GGIO3302$ISCSO
q
Quality
ST
3010013110041005
Qual_Val
Ctrl/GGIO3302$ISCSO
t
Timestamp
ST
2003019010001006
SYS_TIME
Ctrl/GGIO3302$ISCSO
stSeld
BOOLEAN
ST
540001000E011D91
GCNT01_TMP_01
Note: Status (ST) is defined in the function constraint (FC) of the IEC 61850.
Drag and drop
Figure 3.7-18 orCat attribute mapped into ISCSO object of GIGO3302
(iii) Mapping input data
The GCNT01 function can receive three commands select, operate, and cancel. Thus, the user
should map the input-point GCNT01_CMM_REQ. Table 3.7-11 shows the input-point
GCNT01_CMM_REQ and the Object reference Ctrl/GIGO3302$ISCSO1; the user should map
the input-point to the Object reference having attributes CO and CF in FC. Figure 3.7-19 shows
how to map a signal.
Note: The attribute is defined in the IEC 61850; CO stands for Control in the
functional constraint (FC).