6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 612 -
SBOw
Oper
Cancel
Origin
stSeld
sboClass (choiceoperate-once)
ctlmodel (choiceSBOes or SBOns )
sboClass can be found by scrolling down.
Figure 3.8-2 LN editing screen for SBO mode (for example)
Defining DIR mode
Figure 3.8-3 exemplifies the settings in LN “LLNO” when the DIR mode is required for the
MDCTRL01 function. In the DIR mode, the following three items should be selected using the
GR-TIEMS:
Oper
origin
ctlmodel (choice DOes or DOns )
Figure 3.8-3 LN editing screen for DIR mode (for example)
(ii) Mapping output data
The user should group the MDCTRL01 signals with regard to GOOSE and REPORT; the user
should map them for the IEC 61850 communication using GR-TIEMS.
Table 3.8-4 shows the required mapping signals in MDCTRL01 function to the IEC 61850
communications. Figure below shows how to map a signal.
Note: Status (ST) is defined in the function constraint (FC) of the IEC 61850 standard.