EasyManua.ls Logo

Toshiba GR200 Series - (i)-2 Output signal to BO

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 621 -
SPOS01 function (Function ID: 510001)
510001 8601011DC6
“SPOS01_OSL_BO_CSF
(510001_8601011DC6)
DEV01_CONTROL_REQ
Command Remote-On-Control
ILK condition (“ON”) passed
Either SBO mode or DIR mode
(e.g., “ctlmodel” in IEC61850*)
In SBO operate
In DIR operate
Selection Failed
510001_7001016D08
510001 7001016D08
SPOS01-On
To BO connection
Input
Output
Selection logic in SPOS01
0.1s
0
t
0.6s
0
t
&
&
&
&
&
Selection success
Automatic sequence control function (AQEQ)§ in progress
ASEQ_MULTI_SEL
Select condition
1
Select command
with ILK condition
Operate command
with ILK condition
Select command
without ILK condition
Operate command
without ILK condition
For SBO operation
For DIR operation
To Wait for a command
For DIR operation
For SBO operation
To Wait for a next
command
Figure 4.1-2 Select ON from the remote-end in SPOS01
††
Note: The software interlocking (ILK) function can provide the operation criteria for
“On”. The ILK function is discussed separately; note that the operation criteria is
defined by the ILK function itself (i.e., the user cannot set the condition).
Note: Aselect condition signal is provided from the select condition scheme. For more
information, see Figure 4.1-13.
§Note: An Automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The SPOS01 operation is blocked for the ASEQ function being
in the operation. For more information of the ASEQ function, see Chapter
Control
and monitoring application: Automatic sequence control function
.
*Note: The SPOS01 function can run in either the “SBO mode or the “DIR mode. The
user can use a signal called ctlmodel when communication is implemented using
IEC61850. To use this signal, the user must map it for IEC61850 communication.
††
Note: To identify the input and output points of the other SPOS logics, see Table 4.1-5
and Table 4.1-9.
Output signal to BO
The SPOS01 function can issue an output Selection success signal at the output point
SPOS01_OSL_BO_CSF, when the SPOS01 function determines that the Remote-ON-
Control signal received is true. If the SPOS01 function determines that the Remote-ON-
Control signal is not true, the SPOS01 function returns to the Wait for a command stage.

Table of Contents

Related product manuals