EasyManua.ls Logo

Toshiba GR200 Series - (iii)-2 Output signal to BO

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 624 -
Input
Output
Select logic in SPOS01
Command Local-On-Control
SPOS01-On
ILK condition (“ON”) passed
ILK bypassing
(Interlock Bypass”)
1≥
ICB_STATE
[SPOS01-CTRAHMI]
SBO
SPOS01 function (Function ID: 510001)
SBO
DIR
&
&
1≥
&
0.1s
0
t
0.6s
0
t
Either SBO mode or DIR mode
(e.g., “ctlmodel” in IEC61850*)
Automatic sequence control function (AQEQ)§ in progress
ASEQ_MULTI_SEL
Select condition
“SPOS01_OSL_BO_CSF
(510001_8601011DC6)
Selection Failed
To BO connection
Selection success
To Wait for a command
Select command
with ILK condition
Operate command
with ILK condition
For SBO operation
For DIR operation
To Wait for a next
command
Figure 4.1-6 Select ‘On’ on the front panel in SPOS01
††
Note: The ILK function provides the operation criteria for “On”. For testing, nullifying
the ILK function is possible using “Interlock bypassing”. “Interlock bypassing” is
indicated by the status ICB in a software switch controller (SOFTSW).
Note: Aselect condition signal is provided from the select condition scheme. For more
information, see Figure 4.1-13.
§Note: An Automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The SPOS01 operation is blocked for the ASEQ function when
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function
.
††
Note: To identify the output signals of the other SPOS logic, see Table 4.1-9.
Output signal to BO
When the select condition signal is true, the SPOS01 function can issue a “Selection success”
signal at the output-point “SPOS01_OSL_BO_CSF”.
Note: The signal “SPOS01_OSL_BO_CSF” is the same as the signal shown in Figure
4.1-2. If the Local-ON-Control” signal is not true, the SPOS01 function returns to
the Wait for a command stage.

Table of Contents

Related product manuals