6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 625 -
(iv) Receiving “Select command Off” from the local-end
Figure 4.1-7 outlines the reception of the select command Off from the local-end.
Signal reception
from the front panel
Select command Off from front panel
Signal output
Select
decision
Success
Failed
Selection logic
Selection logics
Cancel logic
Wait for a next command
Cancel command
Wait for a command
Operate logic
Operate command
Cancel logic
Operate logic
Select command On from remote-end
Select command On from front panel
Select command On by the PLC
Select command Off by the PLC
Select command Off from remote-end
Figure 4.1-7 Outline of select command ‘Off’
Input signal generated at the local-end.
Figure 4.1-8 shows the select logic when a “Select command Off (Local-OFF-Control) signal is
applied to the SPOS01 function. The signal is provided when the user presses a “OFF key on
the IED front panel; the user is not required to map the signal from IEC61850 communication.
Input
Output
Select logic in SPOS01
Command Local-Off-Control
1≥
[SPOS01-CTRAHMI]
SBO
SPOS01 function (Function ID: 510001)
SBO
DIR
&
&
1≥
&
0.1s
0
0.6s
0
SPOS01-Off
ILK condition (“Off”) passed
ILK bypassing
(Interlock Bypass”)
ICB_STATE
Either SBO mode or DIR mode
(e.g., “ctlmodel” in IEC61850*)
Automatic sequence control function (AQEQ)§ in progress
ASEQ_MULTI_SEL
t
t
“SPOS01_FSL_BO_CSF
(510001_8601011DC6)
Selection Failed
To BO connection
Selection success
To Wait for a command
Select condition
Select command
with ILK condition
Operate command
with ILK condition
For SBO operation
For DIR operation
Figure 4.1-8 Select ‘Off on the front panel in SPOS01
††
Note: The software interlocking (ILK) function can provide the operation criteria for
“Off”. The ILK function is discussed separately; note that the operation criteria is
defined by the ILK function itself (i.e., the user cannot set the condition).