6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 636 -
is true. Another “Operation failed signal is issued at the monitoring point SPOS01_CC_FS
if the SPOS01 function is able to determine that the Remote-cancel signal is not true.
(ii) Receiving “Cancel” from the local-end
Figure 4.1-16 outlines the reception of the cancel command from the local end.
Press cancel
command
Cancel from the front panel
Do nothing
Cancel
decision
Success
Failed
Cancel logic
Wait for a command
Operate logic
Operate command
Operate logic
Select logics
Selecting Off from remote-end
Selecting On from remote-end
Selecting Off from front panel
Selecting On from front panel
Selecting On by the PLC function
Selecting Off by the PLC function
Cancel from the remote end
Wait for a next command
Figure 4.1-16 Outline of ‘cancel command from the local-end
Input signal generated at the local-end
Figure 4.1-17 depicts the cancel logic when a Cancel command (Local-cancel)” signal is applied
to the SPOS01 function. The signal is generated when the Cancel key is pressed on the IED
front panel; the user is not required to take account of mapping. When the logic receives the
Local-cancel signal, the logic is able to output a result signal; provided that the cancel
condition checking is satisfied.
SPOS01 function (Function ID: 510001)
“SPOS01_ CC_SS (510001_8601011E95)
Cancel command
510001 7001016D08
Input
Output
Cancel logic in SPOS01
Cancel condition
&
&
Successes to cancel
Operation Failed
“SPOS01_CC_FS (510001_8701011E96)
Command Local-cancel
Do nothing
To Wait for a command
Figure 4.1-17 ‘Cancel’ from the front panel
Output signal to BO
The SPOS01 function, illustrated in Figure 4.1-17, is able to issue a “Select to cancelsignal
at the monitoring point “SPOS01_CC_SS”, when the SPOS01 function determines that the
Local-Cancel signal is true.