Toshiba GR200 Series - (iii)-1 Input signal generated at the local-end.

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 644 -
Signal reception from
the front panel
Operate command On from the local-end
Do nothing
Operation
decision
Success
Failed
Operate logic
Wait for a command
Signal output
Operate command Off from the local-end
Operate command Off from the local-end
Operate command On by the PLC function
Operate command Off by the PLC function
Wait for a next command
Select stage
Select command Off from the remote-end
Select command On from the remote-end
Select command Off from the local-end
Select command On from the local-end
Select command On by the PLC function
Select command Off by the PLC function
Operate command On from the local-end
Figure 4.1-23 Outline of operate command On
Input signal generated at the local-end.
Figure 4.1-24 illustrates the operate logic when an Operate command On (Local-ON-Control)
signal is applied to the SPOS01 function. The signal is generated when Execution of On is
keyed on the IED front panel.
SPOS1 function (Function ID: 510001)
Assign to BOs
Operate Cmd.
with ILK condition
[SPOS01-PLSM]*
Var
Fix
Latch
S
R
S
R
Operation Failed
0.1 50.0 s
[SPOS01-RST]
[SPOS01-CPW]
Operation Cmd.
without ILK condition
Operate condition
[SPOS01-LGCTRCON]
Fixedlogic
Fixedlogic
[SPOS01-LGCFEXOT]
PLC#2
Command Local-On-Control
ILK condition (“ON”) passed
SPOS01-On
ASEQ function§ is in progress
ASEQ_MULTI_SEL
SPOS01IN_TMP_35
510001 810101EE57
User configurable condition (PLC#1 connection point)
SPOS01IN_TMP_42
510001 810101EDDA
SPOS01-EX_CMP
(5A0101_8001011E93)
SPOS01-FEX_BO
(510001_8101011DD0)
SPOS01-OEC_OK_CSF
(510001_8001011E7F)
&
&
1
&
1
1
&
&
&
&
&
SPOS01_OEX_BO
(510001_8201011DD3) §§
SPOS01_EX_FFL
(510001_8601011E91)
††
To PLC
logic
Input
Output
Operate logic in SPOS01
PLC#1
1
ILK bypassing ( Bypass)
ICB_STATE
0
t
1.0s- 100.0s
User configurable condition (PLC#2 connection point)
To BO connection
To Wait for a command
Figure 4.1-24 Operate On on the front panel
Note: The ILK function provides the operation criteria for “On”.