- 44 -
Figure 2.3-3 Generation of trip signal in the DIFGL function
†Note: The TRC function is discussed separately. See
Chapter Relay application: Trip
circuit
.
(iv) Trip mode
The trip signal generated in the DIFGL function is a “three-phase trip (DIFGL-TRIP)” singnal.
The “three-phase trip” signal switches off the CB in the three-poles.
(v) Operation switch
The user should set On for scheme switch [DIFGL-EN]† prior to the DIFGL operation; the
scheme switch is also illustrated in Figure 2.3-3.
Note: Also, see Chapter
Relay application: Communication application (COMM_APPL)
.
(vi) Setting for autoreclose function
When autoreclose function (ARC) is provided together with the DIFGL function, the ARC
function can re-close the CB again after tripping the CB. When the user wishes to operate the
ARC function, the user should set Non for scheme switch [DIFGL-ARCBlk]. On the other hand,
the user wishes to not to operate the ARC function during the DIFGL operation, set Block for
the scheme switch [DIFGL-ARCBlk] so that a block signal “DIFGL-ARC-BLOCK” is generated
and injected to the autoreclose function (ARC). The ARC function is discussed separately. (See
Chapter
Relay application: Autoreclose function
)